Installation Guide

Power Monitoring

H81xx

TM

Optional Comm Board (sold separately)

Model

Description

H8163-CB

Modbus® Communications Board for H81xx Series

H8186-CB

BACnet® Communications Board for H81xx Series

H8126-CB

Metasys® N2 Communications Board for H81xx Series (consult factory if ordering this item)

Optional Accessory

Model

Description

AH06

Mounting Bracket Kit (fits the Small, Medium, and Large CTs only)

Product Identification 
(cont.)

Specifications

INPUTS

   H8150

90 to 132VAC line-to-neutral

   H8163, H8167

90 to 300VAC line-to-neutral 

   Frequency

50/60 Hz

ACCURACY

   System Accuracy

±1% of reading from 2% to 100% of the CT current rating *

   Sample Rate

1280 Hz

OUTPUTS

   All Models

1.2” x 3.8” (31 mm x 97 mm) viewing area, 160 segments, backlit LCD

   H8163 and H8167

PULSE OUTPUT

PULSE RATE

PULSE WIDTH

PHASE LOSS ALARM OUTPUT

N.O., Opto-FET, 100mA@24VAC/DC

0.10, 0.25, 0.50, 1.00 kWh per pulse (jumper selectable)
200msec closed

H8163: N.O. (opens on alarm, remains open while alarm persists);
H8167: N.C. (closes on alarm, remains closed while alarm persists);

Both H8163 and H8167: Opto-Fet, 100mA@24VAC/DC;

Fixed threshold 25% below any other phase

MECHANICAL

   Protection Class

NEMA 1

   Insulation Class

600 VAC **

OPERATING CONDITIONS

   Operating Temperature Range

0° to 50°C (32° to 122°F)

   Storage Temperature Range

-40°C to 70°C (-40° to 158°F)

   Humidity Range

0-95% RH, non-condensing

   Altitude of Operation

0 to 2000 m

ELECTRICAL SERVICES

   H8150

120/240 VAC with neutral, 208Y/120 VAC line-to-neutral

   H8163, H8167

Any Wye service in which the phase L-N voltage is 

300VAC and the phase-to-

phase voltage is 

480 VAC nom. with neutral

COMPLIANCE INFORMATION

Agency Approvals

UL 61010

Installation Category

Cat III, pollution degree 2

* Meters and current transformers are calibrated as a set. To achieve this accuracy, match the serial numbers on the current 

transformers and the meter at the time of installation (does not apply to 100 A CTs). 

** Do not apply 600V class current transformers to circuits having a phase-to-phase voltage greater than 600V without adequate 

additional insulation between primary conductor and current transformers.

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...