Installation Guide

Power Monitoring

H81xx

TM

Installation

 Disconnect and lock out all power sources during installation and configuration.
 If making connections to the meter through more than one metallic conduit, use a bonding 

plate (Veris part number AH11 or equivalent) to prevent electric shock. 

1.  Verify that the serial number on the meter matches the serial numbers on the current transformers (CTs). These are calibrated 

as a set, and mixing transformers with non-matching meters may damage the device when power is applied. The meter’s serial 

number is printed on the label affixed to the inside of the front cover, and the CT serial number is on the CT label. If using 100 A 

CTs, serial number matching does not apply.

Match serial numbers 

between meters and CTs. 

Serial number matching does 

not apply if using 100 A CTs.

2.   Mount the meter.

3.  Attach the CTs to the conductors. Local code requirements may require a mounting bracket. For maximum accuracy, run the 

conductor through the center of the current transformer window.

4.  Optional step, per NEC and local regulations:

  Attach external fuses (not included with the H81xx devices). Verify that the fuse 

rating is adequate for the applied voltage, with a current rating of ½ Amp (T) slow blow. Select fuses with a fault current rating 

that matches the power source rating.

ØA

ØB

ØC
N

Installer Supplied Fuses

1/2A (T) SLO-BLO

Use fuses compatible with this meter:
Single phase   

Veris AH02

Two phase   

Veris AH03

Three phase   

Veris AH04

VERIS INDUSTRIES

1-800-354-8556

Accessory bonding

plate or equivalent 

required when more 

than one metallic

conduit will be used.

Bond multiple

metallic conduit

runs with available

bonding plate

(Veris AH11 or equivalent)

CONTROLLER

Shock Hazard!

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...

Отзывы: