Installation Guide

Power Monitoring

H81xx

TM

Problem

Solution

No display

· Check external fuses.
· Verify that the display cable has not been disconnected during installation.
· Verify voltage leads are properly connected.

Reported power too low

· Verify CTs and terminals are color-matched.
· Check for phase loss.
· Check external fuses.

Reported power inaccurate

Verify meter and CTs have matching serial numbers (serial number matching does not apply if using 

100 A CTs).

Accuracy not as specified

· Verify CTs and terminals are color-matched.
· Verify that no stray conductive materials (wire clippings, etc.) have shorted between the terminals.

No Pulse output (H8163 and H8167)

· Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.
· The pulse output internal is 200 msec; verify the controller accepts this signal as input.

Pulse output wrong, display OK (H8163  

and H8167)

Set the pulse rate switch and the controller to match kWh/pulse.

No Phase Loss output (H8163  and 

H8167)

Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.

“bAd” appears in the display (H8163  

and H8167)

Verify that the Pulse Rate slide switch is set to a valid value. 0.1 is not valid for 1600 A systems; 0.1 

and 0.25 are not valid for 2400 A systems.

Accuracy not as specified

Verify current transformers and terminals are color-matched.

Troubleshooting

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...

Отзывы: