Installation Guide

Power Monitoring

H81xx

TM

The following messages remain on the lower display for the duration of an alarm condition:

Message

Explanation

Phase loss

The voltage on one phase is less than 75% of the voltage on any other 

phase. The displayed message indicates the problem phase.

Amps Over

The measured current is greater than 110% of the transformer range. The 

display message indicates the problem phase.

Volts Over

Volts A-C, B-C, or A-C is greater than 660VAC.

*

 The displayed message 

indicates the problem phase.

*

 The H8163 and H8167 are rated to 300 VAC L-N, and the H8150 is rated to 132 VAC L-N. Operation above these levels damages the device.

Alarms

The H81xx continually reports kWh or MWh, depending on the total accumulated energy. A secondary display cycles through other 
parameters. The meter has two modes of display operation, depending on the setting of the Display Data jumper (J8) on the main 
circuit board. In Full Display mode, the meter cycles through all parameters. In Plain Display mode, the meter cycles through only 
the first five parameters as listed below: 

kW
Max. kW
PF
Volts
Amps
kVAR
kW, phase A *
kW, phase B *
kW, phase C **
PF, phase A *
PF, phase B *
PF, phase C **
Volts, A-B **
Volts, B-C **
Volts, A-C **
Volts, A-N *
Volts, B-N *
Volts, C-N **
Amps, A *
Amps, B *
Amps, C **

If the H81xx has a communication board installed, every 10th rotation of parameters displays an additional set of data values:

Pulse Rate ***
Address 
Baud Rate
Parity
2/4 Wire

* For meters with 2 or 3 current transformers.
** For meters with 3 current transformers.
*** H8163 and H8167 only.

Data Outputs

www.calcert.com

[email protected]

1.888.610.7664

0

5

10

15

20

25

30

Содержание H81 Series

Страница 1: ...H81xx from the supply source Place this device in close proximity to the equipment and within easy reach of the operator and mark it as the disconnecting device The disconnecting device shall meet th...

Страница 2: ...mA 24VAC DC 0 10 0 25 0 50 1 00 kWh per pulse jumper selectable 200msec closed H8163 N O opens on alarm remains open while alarm persists H8167 N C closes on alarm remains closed while alarm persists...

Страница 3: ...211mm 14 8 375 mm Dimensions A B E F C D B E F C D A A B E C F D A 2 6 66mm B 1 1 28mm C 0 8 19mm D 1 27mm E 2 9 74mm F 3 5 90mm MINI 200Amp A 4 9 124mm B 2 9 73mm C 2 5 62mm D 1 1 29mm E 5 6 141mm F...

Страница 4: ...Phase loss output alarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulse rate selection switch Set the pulse output at 0 1 0 25 0 50 or 1 pulse kWh to match resolutio...

Страница 5: ...erial number is on the CT label If using 100 A CTs serial number matching does not apply Matchserialnumbers betweenmetersandCTs Serialnumbermatchingdoes notapplyifusing100ACTs 2 Mount the meter 3 Atta...

Страница 6: ...tem The Pulse Output is normally open For the H8163 the Phase Loss Output is normally open and for the H8167 it is normally closed Both are rated for 24 VAC VDC 100 mA maximum Ensure that the installa...

Страница 7: ...25 0 1 11 Secure the meter cover shut using a padlock wire tie or other locking device 12 Apply power to the meter 13 Check the display At initial power up the meter checks each phase If the phasing...

Страница 8: ...low wire to Wiring Typical120VAC 2 Wire 1 Installation N A A B C B C N A B C Red Black Yellow Red Black White Yellow RED CT WHITE A N External fuse provided by installer optional per NEC and local reg...

Страница 9: ...00 VAC L N and the H8150 is rated to 132 VAC L N Operation above these levels damages the device Alarms The H81xx continually reports kWh or MWh depending on the total accumulated energy A secondary d...

Страница 10: ...s Accuracy not as specified Verify CTs and terminals are color matched Verify that no stray conductive materials wire clippings etc have shorted between the terminals No Pulse output H8163 and H8167 V...

Отзывы: