manualshive.com logo in svg
background image

ZL0103-0C 

Page 16 of 26 

©2014 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 09141 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

Daisy-chaining Devices to the Power Meter 

The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 2-wire devices. 

+

S

120 Ω terminator on the first and last 

device of the daisy chain

Shield wire

Notes

•  The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications 

standard.

•  The RS-485 transceivers are ¼ unit load or less.

•  RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down to Shield (RS-485 signal ground).

•  Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 Ω termination resistors at each 

end of the bus (not included). 

•  Shield is not internally connected to Earth Ground.

•  Connect Shield to Earth Ground somewhere on the RS-485 bus.

For all terminals:

•  When tightening terminals, apply the correct torque: 0.37 to 0.44 

ft·lb (0.5-0.6 N·m).

•  Use 14-24 gauge (2.1-0.2 mm

2

) wire.

RS-485 
Communications
(E50Cx only)

Red

Black

 

Gray

 

0.37

–0.44 ft•lb

(0.5–0.6 

N•

m)

Use 14-24 gauge wire

Data Logging 
(E50C3 only)

The E50C3 includes a data logging feature that records 10 meter parameters, each in its own buffer. 

Configuration

Use register 150 to set the data logging time subinterval. Writing to the storage buffer is triggered by the subinterval timer. The 
default subinterval is 15 minutes (at a 15 minute interval setting, the buffers hold 60 days of data). An external timer can be used 
over Modbus by setting this register to 0.

Use register 159 to turn on data logging and select either Single Shot or Continuous mode. (default is data logging on, Continuous 
mode). In Single Shot mode, the meter records data until the buffer is full. When the buffer is full, the meter stops recording 
new readings. Data for this time period is kept, but newer energy information is lost. In Continuous mode, the meter continues 
to record energy data as long as the meter is operating. The buffer can only hold 5760 entries at one time, however, so when the 
number of records exceeds 5760, the oldest entry is deleted to make room for the newest.

Registers 169-178 contain the pointers to 10 data storage buffers. Each buffer is user-configurable with the Modbus address of the 
16-bit data output to be stored. 32-bit data, such as floating point data or 32-bit integer energy accumulators, require two buffers. 
However, the lower 16 bits of an integer energy accumulator can be stored in a single buffer (optional).

When the E50C3 is first installed, the buffers contain QNAN data, with a value of 0x8000. This data is considered invalid. If the 
buffer is reset at any point, all entries in the buffers are overwritten with this 0x8000 value, indicating that it is invalid. All invalid 
data is overwritten as the meter fills the buffer with new data entries. 

Reading Data 

Use register 158 to choose which buffer to read. When this register value is set to 0, the meter is in data logging mode. Changing 
this value from 0 to (1 through 10) switches the meter to reading mode and selects a buffer to read. Data from the selected buffer 
appears in registers 8000 to 13760.  

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...

Отзывы: