Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 043*

R

NV ULong

0-0xFFFF

Pulse Counter 1 (Real Energy)

MSR Contact Closure Counters. Valid for 

both Pulse inputs and outputs. E50xx 

counts are shown in (). See register 

144 (Energy per Pulse) for the Wh per 

pulse count. Clear via register 129. 

Inputs are user defined.

• 044*

LSR

• 045*

R

NV ULong

0-0xFFFF

Pulse Counter 2 (Reactive Energy)

MSR

• 046*

LSR

• 047*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption 
Phase A

MSR

Clear via reset register

• 048*

LSR

• 049*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption 
Phase B

MSR

• 050*

LSR

• 051*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption 
Phase C

MSR

• 052*

LSR

Configuration

• 129

R/W

UInt

N/A

Command Register:
- Write 30078 (0x757E) to clear all Energy Accumulators to 0. 
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle. Takes effect at the end of the next 

1 second calculation cycle. Write no more frequently than every 10 seconds.

- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes effect at the end of the 

next 1 second calculation cycle. Write no more frequently than every 10 seconds.

- Write 16640 (0x4100) to Reset Logging (E50C3 only).
- Write 16498 (0x4072) to Clear Pulse Counters to 0.
- Read always returns 0.

• 130

R/W NV UInt

10,
11,
12,
31,
40

Single Phase: A + N

System Type
(See Manual. Note: only the indicated 

phases are monitored for Phase Loss)

Single Phase: A + B
Single Split Phase: A + B + N
3 phase ∆, A + B + C, no N
3 phase Y, A + B + C + N

• 131

R/W NV UInt

Amps

1-32000

CT Ratio – Primary

Current Inputs

• 132

R/W NV UInt

1, 3

CT Ratio – Secondary  Interface (1 or 1/3 V, may not be user 

configurable)

• 133

R/W NV UInt

100

0.01-320.00 PT Ratio:  The meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1). The 

default is 100 (1.00:1), which is with no PT attached. Set this value before setting the system voltage (below)

• 134

R/W NV UInt

82-32000

System Voltage:  This voltage is line to line, except for system type 10 which is line to neutral. The meter uses 

this value to calculate the full scale power for the analog outputs and pulse configuration (below), and as full 

scale for phase loss (register 142). The meter will refuse voltages that are outside the range of 82-660 volts 

when divided by the PT Ratio (above).

• 135

R

NV UInt

kW

W

1-32767

Theoretical Maximum System Power: This read-only value is the theoretical max. power the meter can expect to 

see on a service. This value is 100% of scale on the analog output (0-5VDC or 4-20mA), if equipped. The meter 

recalculates this value if the user changes the CT size, system type, or system voltage. This integer value has 

the same scale as other integer power registers (see register 140 for power scaling).

• 136

R

UInt

Reserved, always returns 0 

• 137

R/W NV UInt

0,1

Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)

Modbus Point Map (cont.)

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...

Отзывы: