Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

Modbus Point Map

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

Integer Data

• 001

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption (MSR) 

 Clear via reset register

• 002

0-0xFFFF

Real Energy Consumption (LSR)

• 003

R

UInt

kW

W

0-32767

Total Instantaneous Real Power (3 Phase Total)

• 004

R

UInt

kVAR

W

0-32767

Total Instantaneous Reactive Power (3 Phase Total)

• 005

R

UInt

kVA

W

0-32767

Total Instantaneous Apparent Power (3 Phase Total)

• 006

R

UInt

Ratio

0.0001

0-10000

Total Power Factor (Total KW / Total KVA)

• 007

R

UInt

Volt

V

0-32767

Voltage, L-L, Average of 3 Phases

• 008

R

UInt

Volt

V

0-32767

Voltage, L-N, Average of 3 Phases

• 009

R

UInt

Amp

I

0-32767

Current, Average of 3 Phases

• 010

R

UInt

kW

W

0-32767

Real Power, Phase A

• 011

R

UInt

kW

W

0-32767

Real Power, Phase B

• 012

R

UInt

kW

W

0-32767

Real Power, Phase C

• 013

R

UInt

Ratio

0.0001

0-10000

Power Factor, Phase A

• 014

R

UInt

Ratio

0.0001

0-10000

Power Factor, Phase B

• 015

R

UInt

Ratio

0.0001

0-10000

Power Factor, Phase C

• 016

R

UInt

Volt

V

0-32767

Voltage, Phase A-B

• 017

R

UInt

Volt

V

0-32767

Voltage, Phase B-C

• 018

R

UInt

Volt

V

0-32767

Voltage, Phase A-C

• 019

R

UInt

Volt

V

0-32767

Voltage, Phase A-N

• 020

R

UInt

Volt

V

0-32767

Voltage, Phase B-N

• 021

R

UInt

Volt

V

0-32767

Voltage, Phase C-N

• 022

R

UInt

Amp

I

0-32767

Current, Instantaneous, Phase A

• 023

R

UInt

Amp

I

0-32767

Current, Instantaneous, Phase B

• 024

R

UInt

Amp

I

0-32767

Current, Instantaneous, Phase C

• 025

R

UInt

Reserved; returns 0x8000 (QNAN)

• 026

R

UInt

Hz

0.01

4500-6500

Frequency (derived from Phase A)

• 027

R

NV ULong

KVAh

E

0-0xFFFF

Apparent Energy Consumption (MSR)

Clear via reset register

• 028

0-0xFFFF

Apparent Energy Consumption (LSR)

• 029

R

NV ULong

KVARh

E

0-0xFFFF

Reactive  Energy Consumption (MSR)

Clear via reset register

• 030

0-0xFFFF

Reactive  Energy Consumption (LSR)

• 031

R

UInt

kVA

W

0-32767

Apparent Power, Phase A

• 032

R

UInt

kVA

W

0-32767

Apparent Power, Phase B

• 033

R

UInt

kVA

W

0-32767

Apparent Power, Phase C

• 034

R

UInt

kVAR

W

0-32767

Reactive Power, Phase A

• 035

R

UInt

kVAR

W

0-32767

Reactive Power, Phase B

• 036

R

UInt

kVAR

W

0-32767

Reactive Power, Phase C

• 037

R

UInt

kW

W

0-32767

Total Real Power Present Demand

• 038

R

UInt

kVAR

W

0-32767

Total Reactive Power Present Demand

• 039

R

UInt

kVA

W

0-32767

Total Apparent Power Present Demand

• 040

R

NV UInt

kW

W

0-32767

Total Real Power Max Demand

• 041

R

NV UInt

kVAR

W

0-32767

Total Reactive Power Max Demand

• 042

R

NV UInt

kVA

W

0-32767

Total Apparent Power Max Demand

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...

Отзывы: