Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 158

R/W NV UInt

0-10

Logging Read Page Register. Selects which of the Register Logs to read (see registers 169-178). 1-10 are valid 

entries that put the meter into log reading mode, temporarily pausing logging. When set to 0 (no variable 

selected for reading), normal logging resumes. The meter will buffer one set of log entries while in reading 

mode if a sub-interval timeout occurs (read/write collision). Default is 0.

Warning:  this buffered data will be written to the log and logging will resume on the following sub-interval 

timeout whether the page register has been cleared or not, resulting in the appearance of data moving in the 

buffer during reads. To avoid this, log buffer reads should be completed and this register set back to 0 in less 

time than the Demand Sub-interval (preferred) or logging should be halted by setting Bit 1 in register 158 

(logs may be missed)

• 159

R/W NV UInt

Logging Configuration Register (Bit Mapped):
Bit 0: Clear to 0 for Continuous log buffer mode. Set to 1 for Single Shot logging mode. Default is 0 (Continuous).
Bit 1: Clear to 0 to enable Logging. Set to 1 to halt logging. Default is 0 (Log).

• 160

R

NV UInt

Logging Status Register (Bit Mapped):
Bit 0: Log buffer full – Set to 1 when one single shot mode has filled the log buffer. The Logged Entry Count will 

continue to increment. Cleared to 0 when logging is restarted (see reset command register 129).

Bit 1: Log Buffer Read Collision 1 – Set to 1 if the meter tried to save log data while the user was reading the 

log (Logging Page Register has been set to something other than 0). On the first collision, the meter holds the 

data until the next sub-interval and then writes the saved data to the log as well as the data for that interval. 

This bit is cleared to 0 on the first demand interval with Logging Page Register = 0. 

Bit 2: Log Buffer Read Collision 2 – Set to 1 on the 2nd attempt to save log data while the user is reading the log 

(Logging Page Register is set to something other than 0). At this point the meter ignores the read condition 

and does a double write, first of the values saved from the previous cycle, and then the present values. If 

the read condition is not removed the meter continues to write the log data as it normally would.  This bit is 

cleared to 0 on the first demand interval with Logging Page Register = 0.

Bit 3: Logging Reset – The Log has been reset during the previous demand sub-interval.
Bit 4: Logging Interrupted – Logging has been interrupted (power cycled, log configuration change, etc.) during 

the previous demand sub-interval.

Bit 5: RTC Changed – The Real Time Clock has been changed during the previous demand sub-interval.
Bit 6: RTC Reset – The Real Time Clock has been reset to the year 2000 and needs to be re-initialized.

• 161

R

NV UInt

0-32767

Log Buffer Wrap / Missed Log Counter. In continous mode, this counter increments each time the internal 

circular log buffer wraps and overwrites old data. The total number of logged entries since the last log reset is: 

(Register 161 x 5760) + Register 163. In single shot mode this counter is the number of log entries lost due to 

the buffer being full. The counter is cleared on logging reset.

• 162

R

NV UInt

0-32767

Max Number of Logging Days. Based on the Sub-Interval Length and the depth of the log buffer, this register 

shows the maximum number of days that data will be logged following a reset until the Buffer is full (Single 

Shot Mode) or overwrites old data (Continuous).

• 163

R

NV UInt

0-32767

Number of Logged Entries since the log buffer wrapped or was reset. In single shot mode, this is the total 

number of valid entries in the buffer. Any entries beyond this will read back as QNAN (0x8000).

• 164

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption (MSR) 

Real Energy (Register 001/002) at the time of the most recent log entries.

• 165

0-0xFFFF

Real Energy Consumption (LSR)

• 166

R

NV UInt

Month / 
Day

See Bytes

Most Significant Byte (MSB)

Least Significant Byte (LSB)

Date & Time of the newest entry in the log. 

After a power cycle, resets to:

Day  01        Month    01
Hour 00        Year    (20) 00

Day 1-31 (0x01-0x1F)

Month 1-12 (0x01-0x0C)

• 167

R

NV UInt

Year /
Hour

See Bytes

Hour 0-23 (0x00-0x17)

Year 0-199 (0x00-0xC7)

• 168

R

NV UInt

Minutes /
Seconds

See Bytes

Seconds 0-59 (0x00-0x3B)

Minutes 0-59 (0x00-0x3B)

Modbus Point Map (cont.)

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...

Отзывы: