Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 146

R

UInt

Diagnostic Alert Bitmap. 1 = Active:
Bit 0:   Phase A Voltage out of range
Bit 1:   Phase B Voltage out of range
Bit 2:   Phase C Voltage out of range
Bit 3:   Phase A Current out of range
Bit 4:   Phase B Current out of range
Bit 5:   Phase C Current out of range
Bit 6:   Frequency out of the range of 45 – 65 Hz OR there is insufficient voltage to determine frequency.
Bit 7:   Reserved for future use 
Bit 8:   Phase Loss A
Bit 9:   Phase Loss B 
Bit 10: Phase Loss C 
Bit 11:  Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12:  Low Power Factor on B
Bit 13:  Low Power Factor on C
Bit 14:   Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power 

(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy 

accumulators (see reset register 129).

Bit 15:  Energy pulse output configuration error (present pulse energy setting may not keep up with the 

theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).

• 147

R

NV UInt

0-32767

Count of Energy Accumulator resets

• 148

R

UInt

Reserved (returns 0)

• 149

R/W NV UInt

1-6

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that 

make a single demand interval. For block demand, set this to 1. 

Demand Calculation

• 150

R/W NV UInt

Seconds

0, 10-32767

Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset 

register (129) to externally re-start the sub-interval. On the E50C3, this is also the 

logging interval.

• 151

R/W

UInt

1-32767

Reserved (returns 0)

• 152

R/W NV UInt

0-32767

Power Up Counter. 

• 153

R

NV UInt

0-32767

Output Configuration. E50B1, E50C2, and E50C3 units have a NO (normally open) energy contact and NC 

(normally closed) (Normally Open - Form A or Normally Closed - Form B) Phase Loss contact. While the relay 

used for the Phase Loss contact is Normally Closed (contacts are closed when the meter is not powered), 

closure indicates the presence of an alarm; either loss of phase, when the meter is powered, or loss of power 

when the meter is not. The contacts are open when the meter is powered and no phase alarm conditions are 

present.

3rd Output:  
0 = RS-485
2 = VAR Pulse

• 154

R

UInt

Reserved, returns 0

Logging Configuration and Status

• 155

R/W NV UInt

Day / 

Month

See Bytes

Most Significant Byte (MSB)

Least Significant Byte (LSB)

Date / Time Clock. Following a power cycle, 

resets to: 

Day  01        Month    01
Hour 00        Year    (20) 00

Day 1-31 (0x01-0x1F)

Month 1-12 (0x01-0x0C)

• 156

R/W NV UInt

Hour / 

Year 

See Bytes

Hour 0-23 (0x00-0x17)

Year 0-199 (0x00-0xC7)

• 157

R/W NV UInt

Seconds / 

Minutes 

See Bytes

 Seconds 0-59 (0x00-0x3B)

Minutes 0-59 (0x00-0x3B)

Modbus Point Map (cont.)

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...