manualshive.com logo in svg
background image

ZL0103-0C 

Page 12 of 26 

©2014 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 09141 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

User Interface for
Data Configuration

*  

This scr

een is not a

vailable in units with firm

war

e v

ersions 1.018 or earlier

.

** 

This scr

een is par

t of the Phase S

ummar

y Da

ta in units with firm

war

e v

ersions 1.018 or earlier

.

*

*

*

_P

H

A

S

APHA

S

BPHA

S

CPHAS

3     A

3  VLL

3  VLN

3    KW

A      A

A

 VA

B

A

    

K

W

1, 2, o

r 3 Phase 

Summary D

ata

Phase

 A:

 

Al

l System

s

Phase

 B

:

&

 3

 Phase

 

System

O

nl

y

Phase C

P

ha

se 

S

ystems

 Onl

y

A

  VL

N

V

ol

ts

 L

in

e-

Li

ne

 (U

(Av

er

ag

of

 Active

 

Phas

es)

 A

m

ps

 (A

)

(Av

er

age

 of

 

Ac

tiv

P

has

es)

V

ol

ts

 L

in

e-

N

eut

ra

l (

V)

 

(A

vera

ge

 o

f Ac

tiv

Ph

as

es

To

ta

l R

ea

Po

w

er

 (P

)

Po

wer

 Fac

tor 

(A

ve

rag

of

 

Active

 P

ha

ses

)

3  

KV

A

Tot

al

 Ap

pa

ren

P

ow

er

 (S

)

B      A

B

 VB

C

B

    

K

W

B

  VL

N

C    

  A

C

 VA

C

C

   

 K

W

C  V

LN

A

  KV

A

B

   

KV

A

C   KVA

A

    

P

F

3    

P

F

B

    

P

F

C

    

P

F

3KVA

R

To

tal

 R

ea

ct

ive

 

P

ow

er

 (Q

)

AKVA

R

BKVA

R

CKVA

R

KVAR

h

K

VA

h

Acc

um

ul

ate

d

R

eac

tiv

e E

ne

rgy

 

(Q

h)

Accumula

te

d

Ap

pa

re

nt 

E

ne

rg

(Sh

)

DEMND

D      KW

P

re

sen

R

eal

 P

ow

er

 

D

em

and

 (P

)

M

     

K

W

M

KVA

R

M

  KV

A

M

ax

im

um

 

Ap

pa

ren

t Po

w

er

 

D

em

and

 (S

)

M

axim

um

 

R

ea

ct

ive

 P

ow

er

 

D

em

an

(Q

)

M

axim

um

 

R

ea

l P

ow

er

 

D

em

an

(P

)

DKVA

R

P

rese

nt

 

Re

ac

tiv

Po

w

er

 

D

em

and

 (Q

)

D  

KV

A

P

res

en

A

ppa

re

nt

 P

ow

er

 

D

em

an

(S

)

DEMND

Dem

and

>>>

  S

cro

ll 

When

 Id

le 

 >

>>

To: 

SE

TU

P

APHA

S

BPHA

S

CP

H

A

S

A

  KW

h

3  

KW

h

B

  KW

h

C

  KW

h

_P

H

A

S

      HZ

Fr

eq

ue

nc

y

Accumula

te

d

R

ea

l E

ne

rg

y

ENRG

Y

To:

A

LE

RT

En

ergy 

Ac

cu

m

ul

at

ors

 

and Co

unters

ENRG

Y

P

UL

S

1

Pu

ls

C

ou

nte

r 1

(W

if 

pr

es

en

t)

P

UL

S

2

P

ul

se

 C

ou

nt

er

 2

(VA

R

if 

pr

es

ent

)

     KWh

Acc

um

ul

ate

d

R

ea

l E

ne

rg

(P

h)

**

**

*

*

**

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...

Отзывы: