Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

UI for Setup (cont.)

Next

Set Passwords:

SETUP -

The Password to enter the SETUP menu.

RESET -

The Password to enter the RESET menu.

RESET

--------

00000

SPASS

Setup

Passwords

SETUP

--------

00000

Back

Next

SDMND

INTRV

--------

6

5

4

3

2

1

Demand

SEC

--------

00900

Back

Set Demand Interval: 

INTRV -

The number of Sub-Intervals (1 to 6) in a 

Demand Interval

.

Default is 1 (block demand).

SEC -

Sub-Interval length in seconds. Default is 

900 (15 minutes).   Set to 0 for external sync-to-

comms (Modbus units only).

Next

S DIS

Display 

Units

UNITS

--------

IEEE

IEC

Back

Set Display Units:  +/-

to switch between: 

IEEE –

VLL VLN  W  VAR  VA Units.

IEC   -

U     V     P     Q     S   Units.

To Setup p. 1 “S  PWR”

Max

PPS 

--------

1

2

5

10

20

50

Pulse

Output

Next

Set Pulse:

The System Type , CT size, PT Ratio, and System Voltage must 

all be configured before setting the Pulse Energy. If any of these 

parameters are changed, the meter will hunt for a new Pulse 

Duration, but will not change the Pulse Energy. If it cannot find a 

solution, the meter will display the wrench, show “ConF” in the 

ALARM -> PULSE screen, and enable Energy pulse output 

configuration error bit in the Modbus Diagnostic Alert Bitmap (if 

equipped).

Wh/P - Set Pulse Energy: 

In Watt Hours (& VAR Hours, if 

present) per Pulse. When moving down to a smaller energy, the 

meter will not allow the selection if it cannot find a pulse duration 

that will allow the pulse output to keep up with Theoretical 

Maximum System Power (see S_PWR screen). When moving 

up to a larger energy, the meter will jump to the first value where 

it can find a valid solution. 

mS/P – Minimum Pulse Duration Time: 

This read only value 

is set by the meter to the slowest duration (in mS per closure) 

that will keep up with the Theoretical Maximum System Power. 

The open time is greater than or equal to the closure time. The 

maximum Pulses Per Second (PPS) is shown in yellow.  

mS/P

--------

500

250

100

50

25

10

SPULS

Back

Wh/P

--------

10000

1000

100

10

SPLOS

Back

IMBAL

--------

0.25

Next

 VOLTS

--------

0.10

Set Phase Loss:

VOLTS - Phase Loss Voltage: 

The fraction of the system 

voltage below which Phase Loss Alarm is on. For system 

types with neutral, the Line to Neutral voltage is also 

calculated and tested. If the System Voltage is 600 and the 

fraction is set to 0.10, then the Phase Loss threshold will be 

60 volts.

IMBAL - Phase Loss Imbalance

: The fractional difference 

in Line to Line voltages above which Phase Loss Alarm is 

on. For system types with neutral, the Line to Neutral 

voltages are also tested. For system types 1+N (10) and 2 

(11) , imbalance is not tested. 

Phase

Loss

Back

 To

  SETU

P

To Setup page 1 “S  CT”, “S COM”, 

or “S BAC” depending on model

BDS

† When leaving this parameter screen using the right button (  ), the display will 
briefly indicate “SAvEd)” to confirm that any changes made have been accepted.

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E50B1

Страница 1: ...ccordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 T...

Страница 2: ...ight 0 62 lb 0 28 kg IP Degree of Protection IEC 60529 IP40 front display IP20 Meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Bl...

Страница 3: ...uts 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu...

Страница 4: ...passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real Reactive and Apparent 3 phase total and per phase Power...

Страница 5: ...uippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back Alarm Energy Two5 characterrows ofdisplaytext Toprowalphanumeric Bottomrownumeric...

Страница 6: ...nted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside The stopping pegs must face t...

Страница 7: ...face or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL...

Страница 8: ...iring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B C N A B C N White Black...

Страница 9: ...al installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeterinputrequirements DCControlPo...

Страница 10: ...d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the CT V screen Use the or buttons to select the vo...

Страница 11: ...powered or loss of power when the meter is not The contacts are open when the meter is powered and no phase loss alarm conditions are present Use an over current protective device rated for the short...

Страница 12: ...lts Line Line U Average of Active Phases Amps A Average of Active Phases Volts Line Neutral V Average of Active Phases Total Real Power P Power Factor Average of Active Phases 3 KVA Total Apparent Pow...

Страница 13: ...eset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Number Energy Pulse Output Error Overrun Error ConF Configuration Error PU...

Страница 14: ...1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT installed See Install for wir...

Страница 15: ...lert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse duratio...

Страница 16: ...rval is 15 minutes at a 15 minute interval setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and...

Страница 17: ...le etc during the previous demand sub interval and whether the Real Time Clock has been changed re initialized to default date time due to a power cycle or modified via Modbus commands Setting Value M...

Страница 18: ...ss byte1 0x11 byte2 bytes following w out crc byte3 ID byte 247 byte4 status 0xFF if the operating system is used status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power...

Страница 19: ...10000 Power Factor Phase C 016 R UInt Volt V 0 32767 Voltage Phase A B 017 R UInt Volt V 0 32767 Voltage Phase B C 018 R UInt Volt V 0 32767 Voltage Phase A C 019 R UInt Volt V 0 32767 Voltage Phase A...

Страница 20: ...to Reset Logging E50C3 only Write 16498 0x4072 to Clear Pulse Counters to 0 Read always returns 0 130 R W NV UInt 10 11 12 31 40 Single Phase A N SystemType See Manual Note only the indicated phases a...

Страница 21: ...more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit in register 146 will be true Phase Loss Output Note The...

Страница 22: ...e energy register 144 147 R NV UInt 0 32767 Count of Energy Accumulator resets 148 R UInt Reserved returns 0 149 R W NV UInt 1 6 Number of Sub Intervals per Demand Interval Sets the number of sub inte...

Страница 23: ...Read Collision 2 Set to 1 on the 2nd attempt to save log data while the user is reading the log Logging Page Register is set to something other than 0 At this point the meter ignores the read conditio...

Страница 24: ...Year Hour 178 R W NV UInt Log Register Pointer 10 Default is 157 Minutes Seconds Floating Point Data 257 258 R NV Float kWh Real Energy Consumption clear via reset register 259 260 R NV Float kWh Rea...

Страница 25: ...eactive Power Max Demand 335 336 R NV Float kVA Total Apparent Power Max Demand 337 338 R Float 0 4294967040 Pulse Counter 1 Real Energy Contact Closure Counters Valid for both Pulse inputs and output...

Страница 26: ...c See the Setup section Incorrect voltage inputs Check power meter voltage input terminals to verify adequate voltage Power meter is wired improperly Check all CTs and PTs to verify correct connection...