E-03
Frequency reference given
auxiliary channel selection
0: Operator keypad digital
1: Potentiometer of keypad
2: Terminal VS1 analog voltage
0-10V
3: Terminal AS analog current signal
4
~
20mA
4: Terminal VS2 analog voltage -10
~
10V
5: Pulse train signal
6: RS485 communication port
7: Up and Down control
8: General PID operation
9: Constant pressure PID control
10: Program running
0
〇
71
103H
E-04
Frequency reference given
channel gain
0.01
~
5.00
1.00
〇
72
104H
E-05
Frequency reference given
channel combination mode
0: Main channel is valid, auxiliary
channel is invalid.
1: Auxiliary channel valid
,
main
channel invalid
2: Both channel is valid if non zero
value, main channel priority
3: Main c K×auxiliary
channel
)
4: main channel -
(
K×auxiliary
channel
)
5: MAX [main channel , (K×auxiliary
channel)]
6: MIN [main channel , (K×auxiliary
channel)]
7: Auxiliary c (K×main
channel)
8: Auxiliary channel - (K×main
channel)
9: MAX [(K×main channel), auxiliary
channel]
10: MIN [(K×main channel), auxiliary
channel]
0
〇
72
105H
E-06
Upper LED monitor selection
0: Frequency Given
1: Output frequency
2: Output current
3: Input voltage
4: Output voltage
5: Machine speed
6: PID given given
7: PID feedback value
0
●
72
106H
E-07
Lower LED monitor selection
1
●
72
107H
E-08
REV/JOG key of keypad
function selection
0: Reverse
1: Jog
0
●
73
108H
E-09
Maximum frequency
0.01
~
600.00Hz
50.00Hz
〇
73
109H
E-10
Upper limit frequency
lower limit frequency
~
maximum
frequency
50.00Hz
●
73
10AH