19
E-30
Starting mode selection
LED unit digit: Starting mode
selection.
0:Starts from starting frequency
1: DC braking first, and then start from
starting frequency
2: Restart after speed search
LED tens digit: Reserve
LED Hundreds digit: Speed
search direction
0: Speed search performs only in
running direction
1: bi-direction speed search
LED Thousands digit: Speed
search mode
0: Software speed search
1: Hardware speed search
※
000
〇
79
11EH
E-31
Power off restart selection
0: Disalbe 1
:
Enalbe
0
●
80
11FH
E-32
Power off restart waiting time
0.0
~
10.0s
0.5s
●
80
120H
E-33
Free stop frequency
0.00
~
60.00Hz
0.00Hz
●
81
121H
E-34
Stop mode
0: Deceleration stop
1: Free stop
0
●
81
122H
E-35
DC braking current
0
~
150%
50%
●
81
123H
E-36
DC braking time when stop
0.0
~
30.0s
0.0s
●
81
124H
E-37
DC braking starting frequency
when stop
0.00
~
60.00Hz
0.00Hz
●
81
125H
E-38
DC braking time when start
0.0
~
10.0s
0.0s
●
81
126H
E-39
Jump frequency 1
0.00
~
600.0Hz(Fmax)
0.00Hz
●
81
127H
E-40
Jump frequency 2
0.00
~
600.0Hz(Fmax)
0.00Hz
●
81
128H
E-41
Jump frequency 3
0.00
~
600.0Hz(Fmax)
0.00Hz
●
81
129H
E-42
Jump frequency range
0.00
~
5.00Hz
0.00Hz
●
82
12AH
E-43
Number of auto restart
attempts
0: Disable
1
~
3: Enable
0
●
82
12BH
E-44
Fault auto reset waiting time
0.1
~
20.0s
1.0s
●
82
12CH
E-45
Machine warm up time
0.0
~
6500s
0.0s
●
83
12DH
E-46
Running direction selection
0: Consistent with the default direction
1: Opposite to the default direction
2: Reverse running forbidden.
0
〇
83
12EH
E-47
FOR/REV dead zone time
0.0
~
10.0s
0.0s
●
83
12FH
E-48
Cooling fans running selection
0: Fan runs when switch on.
1: Fan runs or not relates with
temperature during inverter stop
mode, fan runs when inverter running.
2.Fan stop during inverter stop mode,
running if not relates with temperature
during inverter ruing
※
●
83