20
E-49
Inverter protecting mode
selection
LED unit digit: Overvoltage
protecting selection during
deceleration
0: Disable 1 Enable
LED ten digit: Output phase
missing protection
0: Disable 1 Enable
LED hundred digit: Input phase
missing protection
0: Disable 1 Enable
LED thousand digit: Inverter
overload, over heat protect mode
selection.
0: Free stop
1: Running with current limit
0
※
11
●
84
131H
E-50
Coefficient value of electronic
thermal
30%
~
120% (disable for value less
than 30 )
0%
●
84
132H
E-51
Stall protecting current limit
value
100%
~
250%
160 G
120 P
●
85
133H
E-52
Stall protecting DC bus voltage
threshold value
105
~
160%
110%
●
85
134H
E-53
Dynamic braking and
decelerating over voltage
suppression threshold voltage
105
~
160%
135%
●
86
135H
E-54
Ratio of dynamic braking
0
~
100%
80%
●
86
136H
E-55
DC bus under voltage
protecting value
60
~
90%
65%
●
86
137H
E-56
Reserve
86
138H
E-57
Reserve
86
139H
E-58
Reserve
86
13AH
E-59
Rotation speed display scale
factor
0.1
~
2000.0%
100.0%
●
86
13BH
E-60
Ratio of inverter output voltage
50
~
110%
100%
〇
86
13CH
E-61
G/P type setting
0
:
G type 1
:
P type
0
〇
86
13DH
E-62
Speed search stabilizing
keeping time
0.200
~
10.000s
0.600s
●
87
13EH
E-63
Parameters change protection
0: All the parameters changing is
allowed
1: Only keyboard digital given
parameter changing allowed
2: All the parameters prohibit changing
0
●
87
13FH
E-64
Parameter initialization
0: Null
1: Restores to factory default setting
value
2: Clear fault record
3: Transfer parameters of inverter to
keypad and save.
4: Transfer parameters saved of
keypad to inverter
0
〇
87
140H