Chapter 1: Summarize 

1.1    Safety requirements and cautions 

To ensure safety of your health, equipment and property, 

please read this chapter carefully 

before use 

the frequency inverter 

and act in compliance with the instructions while carrying, installing, debugging, 

running and overhauling 

the 

frequency inverter. 

Warn sign and meaning 

 

Danger: it will cause danger of serious injuries and even death while 
operating against the rules 

 

Caution:  it  will  cause  danger  of  light  injuries  or  equipment 
destruction while operating against the rules 

Qualified operation 

Only qualified person after professional train can operate the equipment.The operator must be with 
professional train, familiar with installation, wiring, running and maintain of equipment, and can deal 
emergency case.   

Safe guide 

Warn sign is for safe, to prevent operator from hurt and prevent this product and relating equipment 
from being damaged. Before operating, be sure to carefully read the manual about safety, installation, 
operation and maintenance and obey to the safe rules and warn sign.   

 

● 

Right transport, store, installation and careful operation and maintenance is most important for inverter safe run. In 

transport and store process, make sure the inverter is free from impact and vibration. It must be stored where is dry, 

without corrosive air and conductive dust, temperature lower than 60

.

 

● 

This  product  carries  dangerous  voltage  and  controls  driver  machine  with  potential  danger.  If  not  abide  the 

regulations or requirements in this manual, there is danger of body injury even death and machine system damage.

 

● 

Do not wire while the power is conneted. Otherwise there is danger of death for electric shock. Before wiring, 

inspection, maintenance, please cut power supply of all related equipments and ensure mains DC voltage in safe 

range. And please do operation after 5 mins.

 

● 

Power wire, motor wire and control wire should be all connected firmly. Earth must be reliable and earth resistance 

must be lower than 10Ω.

 

● 

Human body electrostatic will seriously damage inner sensitive components. Before operation, please follow ESD 

measures. Otherwise there is danger of iverter damage.

 

● 

Inverter  output  voltage  is  pulse  wave.  If  components  such  as  capacitor  what  improves  power  factor  and 

pressure-sensitive resistance for anti-thunder and so on are installed at the output side, please dismantle or change 

to input side.

 

● 

No switch components such as breaker and contactor at the output side. (If there must be one, please make sure 

the output current is 0 while the switch acting).

 

● 

No matter where the fault is, there is danger of serious accident, even human body injury what means dangerous 

malfunction possibility. So there must be additional external prevent measures or other safety devices, such as 

independent current limiting switch, machinery fense and so on.

 

● 

Only used in application fields as maker stated. No use in equipments related to special fields such as emergency, 

succor, ship, medical treatment, avigation, nuclear and etc.

 

● 

Only service department of the maker or its authorized service center or professional person trained and authorized 

Содержание AC70E-S2-1R5G

Страница 1: ...messages of installing wiring keyboard operation simple function table troubleshooting maintenance only For parameters setting detail pls read AC70 general used series manual or consult us For the bes...

Страница 2: ...anger If not abide the regulations or requirements in this manual there is danger of body injuryeven death and machinesystemdamage Do not wire while the power is conneted Otherwise there is danger of...

Страница 3: ...e is ok pls open it and check the inverter If damage caused in transport it is not duty of Veich company But please contact Veich or the transport company immediately After checking the product please...

Страница 4: ...age compensation function if motor rated voltage is 100 the voltage can be set in the 50 100 scope the voltage output should not exceed the input voltage AVR adjust When the grid voltage fluctuates ch...

Страница 5: ...and avoid the impact of electromagnetic interference Ensure all equipments connected to frequency inverter are connected to star earth or common earth bus by short and thick cable as well as frequenc...

Страница 6: ...c condition of safe and reliable running of the product For right earthing please read the following notice carefully In order to avoid electric shock earthing cable should be the size as electric equ...

Страница 7: ...e without metal dust oil water or etc into inverter please do not install inverter on flammable material such as food and etc Place without radioactive material or flammablematerial Place without pois...

Страница 8: ...inverter cooling please follow installation conditions as below It should adopts hanging style or closet style with upright installation and keeps enough space with surroundings or the wall Multi inve...

Страница 9: ...inverter and keyboard W1 H 1 W H D D1 MODEL WW W1 H H1 D D1 INSTALLATION APERTURE AC70E S2 R40G 88 75 142 5 129 5 142 132 5 AC70E S2 R75G AC70E S2 1R5G AC70E T3 R75G AC70E T3 1R5G AC70E S2 2R2G 106 90...

Страница 10: ...to obey aimed to ensuring safe use best performance and reliable running Note Analog monitor output is special output of meters such as frequcy meter current meter voltage meter and etc It can not be...

Страница 11: ...0 75 kW 200 120W 100 1 5 kW 400 300W 100 1 5 kW 100 300W 100 2 2 kW 250 400W 100 2 2 kW 75 300W 100 3 7 kW 150 500W 100 Main circuit terminals Terminal Name Function definition Braking resistance ter...

Страница 12: ...amme set definition Pls refer F 01 F 04 X2 Multi function contact input X2 X3 Multi function contact input X3 X4 Multi function contact input X4 AO Analog output Physical type of output signal 0 10V 0...

Страница 13: ...oring state While given frequency or PID or given torque are set by keyboard Shift key Select digit of function no modified by up down key Select parameter digits modified by up dowm key Change LED mo...

Страница 14: ...ator and the A indicator light at the same time display value is the motor speed Flashing When the A indicator and the V indicator flashing at the same time display value is gived PID value On When th...

Страница 15: ...tting range and definition Factary default pr op ert y Refer to page Comm unicati on code E 00 Control method selection 0 Open loop vector controlwithout PG 1 V F control mode 1 69 100H E 01 Running c...

Страница 16: ...Both channel is valid if non zero value main channelpriority 3 Main channel K auxiliary channel 4 main channel K auxiliary channel 5 MAX main channel K auxiliary channel 6 MIN main channel K auxiliar...

Страница 17: ...elerate decelerate time datum point 0 Motor rated frequency 1 Maximum frequency LED hundreds digit Equidistance stop function 0 Disable 1 Enable LEDThousands digit reserve 0000 74 10FH E 16 Frequencyg...

Страница 18: ...shock is enabled 1010 77 115H E 22 V F slip compensation 0 200 100 78 116H E 23 Energy saving mode selection LED unitdigit Auto energy saving selection 0 disable 1 enable LED tens digit V F slip compe...

Страница 19: ...ng starting frequency when stop 0 00 60 00Hz 0 00Hz 81 125H E 38 DC braking time when start 0 0 10 0s 0 0s 81 126H E 39 Jump frequency 1 0 00 600 0Hz Fmax 0 00Hz 81 127H E 40 Jump frequency 2 0 00 600...

Страница 20: ...tage suppression threshold voltage 105 160 135 86 135H E 54 Ratio of dynamicbraking 0 100 80 86 136H E 55 DC bus under voltage protecting value 60 90 65 86 137H E 56 Reserve 86 138H E 57 Reserve 86 13...

Страница 21: ...ent in deceleration suppression 0 Disable 1 Enable 2 Enable frequency reducing for protecting over current 0001 91 143H External terminal parameters Code funcion Fucntion name Setting range and define...

Страница 22: ...2 18 Frequency main channel selection terminal3 19 Frequency main channel selection terminal4 20 Program running pause 21 Program restart 22 Timer trigger terminal 23 Timer reset terminal 24 Counter r...

Страница 23: ...ute UP DW adjusting LED hundred digit STOP RESE of keypad effective range selection 0 STOP RESE key valid only when under keypad control 1 STOP RESE key valid underany run command source LED thousand...

Страница 24: ...educing acceleration time 0 1 6500 0s 1 0s 97 217H F 24 Acceleration time 2 0 1 6500 0s 98 218H F 25 Deceleration time 2 98 219H F 26 Acceleration time 3 98 21AH F 27 Deceleration time 3 98 21BH F 28...

Страница 25: ...inal input voltage lower limit 0 00V F 42 0 50V 101 229H F 42 VS1 terminal input voltage upper limit F 41 10 00V 9 50V 101 22AH F 43 VS1 terminal input voltage gain 0 01 5 00 1 00 101 22BH F 44 VS2 te...

Страница 26: ...0 Positive characteristic 1 Negative characteristic LED ten digit AS input characteristic selection 0 Positive characteristic 1 Negative characteristic LED hundred digit VS2 input characteristic sele...

Страница 27: ...5 00 1 00 106 245H F 70 UP DW terminalpreset frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 246H F 71 UP DW Power off memorized frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 247H Special functi...

Страница 28: ...20 Integral time constant I 0 1 100 0s 2 0s 109 314H H 21 Differentialgain D 0 0 10 0 0 0 109 315H H 22 Sampling period 0 01 60 00s 0 10s 110 316H H 23 PID controldeviation limit 0 0 20 0 0 0 110 317...

Страница 29: ...step speed direction and accel decel time 4 113 327H H 40 6 step speed direction and accel decel time 5 113 328H H 41 7 step speed direction and accel decel time 6 113 329H H 42 8 step speed directio...

Страница 30: ...rate 0 1200bps 1 2400bps 2 4800bps 3 9600bps 4 19200bps 5 38400bps 3 116 345H H 70 Communication setting frequency ratio 0 00 20 00 1 00 116 346H H 71 Time of communication time out 0 0 6500 0s 10 0s...

Страница 31: ...tionover limit Prolong Deceleration time Reduce load inertiaor improve inverter capacitanceor add braking unit Detectpowervoltage and clear fault E oU3 Constant speedover volt age Power voltage fluctu...

Страница 32: ...isdamaged Electromagneticdisturb Prolong acceleration time Checkperipheryequipments and restart afrer fault cleared Seeksupport from factory Check system wiring earth shield and dealas required E oH...

Страница 33: ...age Check keyboard wire Seeksupport from factory E CPE Parameter copy fault Parameter copy communication is fault Copy keyboard is not match the inverter Check wire Select the specified external keybo...

Страница 34: ...n periodic Main circuit panorama If the fastener loosen whether having the hot shot trail whether having discharging or not phenomenon dust are too much if the wind way is blocked up Visual tighten cl...

Страница 35: ...volt megger measures the frequency inverter Its insulation resistance should not smaller than 4M When using the general ohmmeters to measure current the current in the input end will has imbalance ph...

Страница 36: ...being authorized by our company When quality problem appears our company only undertakes three guarantee service as the 11 1 and 11 2 responsibilities above If user needs more responsibility guarantee...

Страница 37: ...tive C07H C 8 PID feedback quantitative C08H C 9 Module temperature C09H C 10 Accumulative operation time hour C0AH C 11 Accumulative operation time after latest power on Min C0BH C 12 Output current...

Страница 38: ...input terminal on off state X1 terminal stage X3 terminal stage X4 terminal stage Output terminal connect disconnect state schematic diagram Reserve Reserve Reserve Reserve Y2 terminal stage Y1 termi...

Страница 39: ...ault Units E07H Er 08 Running direction while the latest fault 0 Forward 1 reverse E08H Er 09 Running status while the latest fault 0 close down 1 stable speed 2 acceleration 3 deceleration E09H Er 10...

Отзывы: