24
F-10
2 step speed setting 2X
0.00Hz
~
upper limit frequency
25.00Hz
●
96
20AH
F-11
3 step speed setting 3X
40.00Hz
●
96
20BH
F-12
4 step speed setting 4X
50.00Hz
●
96
20CH
F-13
5 step speed setting 5X
50.00Hz
●
96
20DH
F-14
6 step speed setting 6X
40.00Hz
●
96
20EH
F-15
7 step speed setting 7X
25.00Hz
●
96
20FH
F-16
8 step speed setting 8X
10.00Hz
●
96
210H
F-17
Reserve
97
211H
F-18
Reserve
97
212H
F-19
Speed search tracking speed
0.1
~
10.0%
0.2%
〇
97
213H
F-20
Voltage stores time
0.10S
~
10.00S
0.60S
〇
97
214H
F-21
Speed search respond current
threshold value
10%
~
200%
120%
〇
97
215H
F-22
Frequency reducing
acceleration time
0.1
~
6500.0s
2.0s
●
97
216H
F-23
Frequency reducing
acceleration time
0.1
~
6500.0s
1.0s
●
97
217H
F-24
Acceleration time 2
0.1
~
6500.0s
※
●
98
218H
F-25
Deceleration time 2
※
●
98
219H
F-26
Acceleration time 3
※
●
98
21AH
F-27
Deceleration time 3
※
●
98
21BH
F-28
Acceleration time 4
※
●
98
21CH
F-29
Deceleration time 4
※
●
98
21DH
F-30
Relay output terminal
(TA,TB,TC)
0: Zero frequency (standby state)
1:Fault alarm 1. (Including fault auto
reset period. )
2: Fault alarm 2. (Not includes fault
auto reset period. )
3: Frequency arriving detection
4: Frequency level detection
5: Running statues
6: Reverse running
7: Under voltage of inverter
8: Overload pre-alarm
9: Output frequency reach upper limit
frequency
10. Output frequency reach lower limit
frequency
11. External fault stop
12. Timer times up
13. Counter reach maximum values
14. Counter reach setting values
15. PID feedback upper limit alarm
1
●
98
21EH
F-31
Output terminal Y1
4
●
98
21FH