29

H-33 

Program run breakpoint 
restore mode selection 

0: Running at the first step speed 
1: Continue to run with breakpoint 
running frequency and retiming. 
2: Continue to run with the breakpoint 
running frequency and residual time. 

 

112 

321H 

H-34 

Program running state power 
down memory selection 

0: NO power down memory   
1: power down memory 

 

113 

322H 

H-35 

1 step speed direction and 
accel/decel time   

0: Forward; Acceleration time 
1/Deceleration time 1 
1: Forward; Acceleration time 
1/Deceleration time 2 
2: Forward; Acceleration time 
1/Deceleration time 3 
3: Forward; Acceleration time 
1/Deceleration time 4 
4: Reverse; Acceleration time 
1/Deceleration time 1 
5: Reverse; Acceleration time 
1/Deceleration time 2 
6: Reverse;    Acceleration time 
1/Deceleration time 3 
7: Reverse;    Acceleration time 
1/Deceleration time 4 

 

113 

323H 

H-36 

2  step  speed  direction  and 
accel/decel time 

 

113 

324H 

H-37 

3  step  speed  direction  and 
accel/decel time 

 

113 

325H 

H-38 

4  step  speed  direction  and 
accel/decel time 

 

113 

326H 

H-39 

5  step  speed  direction  and 
accel/decel time 

 

113 

327H 

H-40 

6  step  speed  direction  and 
accel/decel time 

 

113 

328H 

H-41 

7  step  speed  direction  and 
accel/decel time 

 

113 

329H 

H-42 

8  step  speed  direction  and 
accel/decel time 

 

113 

32AH 

H-43 

1 step speed running time T1 

0.0

6000s(min) 

10.0 

 

113 

32BH 

H-44 

2 step speed running time T2 

10.0 

 

113 

32CH 

H-45 

3 step speed running time T3 

10.0 

 

113 

32DH 

H-46 

4 step speed running time T4 

10.0 

 

113 

32EH 

H-47 

5 step speed running time T5 

10.0 

 

114 

32FH 

H-48 

6 step speed running time T6 

10.0 

 

114 

330H 

H-49 

7 step speed running time T7 

10.0 

 

114 

331H 

H-50 

8 step speed running time T8 

10.0 

 

114 

332H 

H-51 

Differential frequency   

∆f    in swing frequency 

0.00

20.00Hz 

2.00Hz 

 

114 

333H 

H-52 

Motor rated power   

0.4

1100.0KW 

 

 

114 

334H 

H-53 

Motor rated frequency   

0.00

600.00Hz 

50.00Hz 

 

114 

335H 

H-54 

Motor rated speed 

0

18000RPM 

 

 

114 

336H 

H-55 

Motor rated voltage 

0

1500V 

 

 

114 

337H 

H-56 

Motor rated current 

0.1

1000.0A 

 

 

114 

338H 

H-57 

Motor no load current 

0.01

650.00A 

 

 

114 

339H 

H-58 

Motor stator resistor   

0.001

65.000Ω 

 

 

114 

33AH 

H-59 

Motor rotator resistor 

0.001

65.000Ω 

 

 

114 

33BH 

H-60 

Motor stator inductance   

0.1

6500.0mH 

 

 

114 

33CH 

H-61 

Motor rotator mutual 
inductance 

0.1

6500.0mH 

 

 

115 

33DH 

Содержание AC70E-S2-1R5G

Страница 1: ...messages of installing wiring keyboard operation simple function table troubleshooting maintenance only For parameters setting detail pls read AC70 general used series manual or consult us For the bes...

Страница 2: ...anger If not abide the regulations or requirements in this manual there is danger of body injuryeven death and machinesystemdamage Do not wire while the power is conneted Otherwise there is danger of...

Страница 3: ...e is ok pls open it and check the inverter If damage caused in transport it is not duty of Veich company But please contact Veich or the transport company immediately After checking the product please...

Страница 4: ...age compensation function if motor rated voltage is 100 the voltage can be set in the 50 100 scope the voltage output should not exceed the input voltage AVR adjust When the grid voltage fluctuates ch...

Страница 5: ...and avoid the impact of electromagnetic interference Ensure all equipments connected to frequency inverter are connected to star earth or common earth bus by short and thick cable as well as frequenc...

Страница 6: ...c condition of safe and reliable running of the product For right earthing please read the following notice carefully In order to avoid electric shock earthing cable should be the size as electric equ...

Страница 7: ...e without metal dust oil water or etc into inverter please do not install inverter on flammable material such as food and etc Place without radioactive material or flammablematerial Place without pois...

Страница 8: ...inverter cooling please follow installation conditions as below It should adopts hanging style or closet style with upright installation and keeps enough space with surroundings or the wall Multi inve...

Страница 9: ...inverter and keyboard W1 H 1 W H D D1 MODEL WW W1 H H1 D D1 INSTALLATION APERTURE AC70E S2 R40G 88 75 142 5 129 5 142 132 5 AC70E S2 R75G AC70E S2 1R5G AC70E T3 R75G AC70E T3 1R5G AC70E S2 2R2G 106 90...

Страница 10: ...to obey aimed to ensuring safe use best performance and reliable running Note Analog monitor output is special output of meters such as frequcy meter current meter voltage meter and etc It can not be...

Страница 11: ...0 75 kW 200 120W 100 1 5 kW 400 300W 100 1 5 kW 100 300W 100 2 2 kW 250 400W 100 2 2 kW 75 300W 100 3 7 kW 150 500W 100 Main circuit terminals Terminal Name Function definition Braking resistance ter...

Страница 12: ...amme set definition Pls refer F 01 F 04 X2 Multi function contact input X2 X3 Multi function contact input X3 X4 Multi function contact input X4 AO Analog output Physical type of output signal 0 10V 0...

Страница 13: ...oring state While given frequency or PID or given torque are set by keyboard Shift key Select digit of function no modified by up down key Select parameter digits modified by up dowm key Change LED mo...

Страница 14: ...ator and the A indicator light at the same time display value is the motor speed Flashing When the A indicator and the V indicator flashing at the same time display value is gived PID value On When th...

Страница 15: ...tting range and definition Factary default pr op ert y Refer to page Comm unicati on code E 00 Control method selection 0 Open loop vector controlwithout PG 1 V F control mode 1 69 100H E 01 Running c...

Страница 16: ...Both channel is valid if non zero value main channelpriority 3 Main channel K auxiliary channel 4 main channel K auxiliary channel 5 MAX main channel K auxiliary channel 6 MIN main channel K auxiliar...

Страница 17: ...elerate decelerate time datum point 0 Motor rated frequency 1 Maximum frequency LED hundreds digit Equidistance stop function 0 Disable 1 Enable LEDThousands digit reserve 0000 74 10FH E 16 Frequencyg...

Страница 18: ...shock is enabled 1010 77 115H E 22 V F slip compensation 0 200 100 78 116H E 23 Energy saving mode selection LED unitdigit Auto energy saving selection 0 disable 1 enable LED tens digit V F slip compe...

Страница 19: ...ng starting frequency when stop 0 00 60 00Hz 0 00Hz 81 125H E 38 DC braking time when start 0 0 10 0s 0 0s 81 126H E 39 Jump frequency 1 0 00 600 0Hz Fmax 0 00Hz 81 127H E 40 Jump frequency 2 0 00 600...

Страница 20: ...tage suppression threshold voltage 105 160 135 86 135H E 54 Ratio of dynamicbraking 0 100 80 86 136H E 55 DC bus under voltage protecting value 60 90 65 86 137H E 56 Reserve 86 138H E 57 Reserve 86 13...

Страница 21: ...ent in deceleration suppression 0 Disable 1 Enable 2 Enable frequency reducing for protecting over current 0001 91 143H External terminal parameters Code funcion Fucntion name Setting range and define...

Страница 22: ...2 18 Frequency main channel selection terminal3 19 Frequency main channel selection terminal4 20 Program running pause 21 Program restart 22 Timer trigger terminal 23 Timer reset terminal 24 Counter r...

Страница 23: ...ute UP DW adjusting LED hundred digit STOP RESE of keypad effective range selection 0 STOP RESE key valid only when under keypad control 1 STOP RESE key valid underany run command source LED thousand...

Страница 24: ...educing acceleration time 0 1 6500 0s 1 0s 97 217H F 24 Acceleration time 2 0 1 6500 0s 98 218H F 25 Deceleration time 2 98 219H F 26 Acceleration time 3 98 21AH F 27 Deceleration time 3 98 21BH F 28...

Страница 25: ...inal input voltage lower limit 0 00V F 42 0 50V 101 229H F 42 VS1 terminal input voltage upper limit F 41 10 00V 9 50V 101 22AH F 43 VS1 terminal input voltage gain 0 01 5 00 1 00 101 22BH F 44 VS2 te...

Страница 26: ...0 Positive characteristic 1 Negative characteristic LED ten digit AS input characteristic selection 0 Positive characteristic 1 Negative characteristic LED hundred digit VS2 input characteristic sele...

Страница 27: ...5 00 1 00 106 245H F 70 UP DW terminalpreset frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 246H F 71 UP DW Power off memorized frequency 0 00Hz upper limit freqeuncy 0 00Hz 106 247H Special functi...

Страница 28: ...20 Integral time constant I 0 1 100 0s 2 0s 109 314H H 21 Differentialgain D 0 0 10 0 0 0 109 315H H 22 Sampling period 0 01 60 00s 0 10s 110 316H H 23 PID controldeviation limit 0 0 20 0 0 0 110 317...

Страница 29: ...step speed direction and accel decel time 4 113 327H H 40 6 step speed direction and accel decel time 5 113 328H H 41 7 step speed direction and accel decel time 6 113 329H H 42 8 step speed directio...

Страница 30: ...rate 0 1200bps 1 2400bps 2 4800bps 3 9600bps 4 19200bps 5 38400bps 3 116 345H H 70 Communication setting frequency ratio 0 00 20 00 1 00 116 346H H 71 Time of communication time out 0 0 6500 0s 10 0s...

Страница 31: ...tionover limit Prolong Deceleration time Reduce load inertiaor improve inverter capacitanceor add braking unit Detectpowervoltage and clear fault E oU3 Constant speedover volt age Power voltage fluctu...

Страница 32: ...isdamaged Electromagneticdisturb Prolong acceleration time Checkperipheryequipments and restart afrer fault cleared Seeksupport from factory Check system wiring earth shield and dealas required E oH...

Страница 33: ...age Check keyboard wire Seeksupport from factory E CPE Parameter copy fault Parameter copy communication is fault Copy keyboard is not match the inverter Check wire Select the specified external keybo...

Страница 34: ...n periodic Main circuit panorama If the fastener loosen whether having the hot shot trail whether having discharging or not phenomenon dust are too much if the wind way is blocked up Visual tighten cl...

Страница 35: ...volt megger measures the frequency inverter Its insulation resistance should not smaller than 4M When using the general ohmmeters to measure current the current in the input end will has imbalance ph...

Страница 36: ...being authorized by our company When quality problem appears our company only undertakes three guarantee service as the 11 1 and 11 2 responsibilities above If user needs more responsibility guarantee...

Страница 37: ...tive C07H C 8 PID feedback quantitative C08H C 9 Module temperature C09H C 10 Accumulative operation time hour C0AH C 11 Accumulative operation time after latest power on Min C0BH C 12 Output current...

Страница 38: ...input terminal on off state X1 terminal stage X3 terminal stage X4 terminal stage Output terminal connect disconnect state schematic diagram Reserve Reserve Reserve Reserve Y2 terminal stage Y1 termi...

Страница 39: ...ault Units E07H Er 08 Running direction while the latest fault 0 Forward 1 reverse E08H Er 09 Running status while the latest fault 0 close down 1 stable speed 2 acceleration 3 deceleration E09H Er 10...

Отзывы: