4
Diagnostics
Relays and Inputs
4-4
Relays and Inputs
The Relays and Inputs diagnostics contain information/diagnostics about relays and inputs.
AVAILABLE DIAGNOSTIC SCREENS
•
External Inputs
- View diagnostic information on external Inputs.
•
Relays
- Test all configured relays (except PLLD relays). Two types of relay tests are available:
- Sequential Test - This test sets selected relays to INACTIVE for two seconds and then sets them to ACTIVE
for two seconds. When the test is complete the relays are automatically reset to their original state.
- Relay Inspection Test - This test sets selected relays to a selectable state, ACTIVE or INACTIVE, until the test
is complete. When you finish the test the relays are automatically reset to their original state.
Sensors
The Sensor diagnostics contain reports on the activity and condition of Liquid, Vapor, Groundwater, 2-wire CL and
3-wire CL sensors. Section 9 of this manual is devoted to sensor troubleshooting.
AVAILABLE SENSOR DIAGNOSTIC REPORTS
•
Liquid (diagnostic information about each Liquid Sensor)
•
Vapor (diagnostic information about each Vapor Sensor)
•
Groundwater (diagnostic information about each Groundwater Sensor)
•
2-Wire CL (diagnostic information about each 2-wire CL sensor)
•
3-Wire CL (diagnostic information about each 3-wire CL sensor)
Tank
The Tank diagnostics contains information related to tank inventory volumes and tank charts.
AVAILABLE TANK DIAGNOSTIC REPORTS
•
30 Second Inventory Samples Report (diagnostic information about 30 second inventory samples)
Tank Test
The Tank Test diagnostics contain information on all environmental tank tests. Each report has quick access to the
appropriate tank test setup screen. Manual tank leak tests are run from this diagnostic.
CSLD and/or SLD tabs will be displayed only if these features are supported and at least one tank has the
respective feature enabled. Current or active reports will not be visible for tanks that are not configured or inactive.
Historic reports will be available for tanks even if they are not configured or if they are inactive.
Section 11 of this manual is devoted to CSLD/SLD troubleshooting.