11-13
11
CSLD Troubleshooting
Contacting Tech Support
Contacting Tech Support
If the CSLD problem cannot be resolved, retrieve the following data via the RS-232 port or SiteFax modem and
contact Technical Support:
1. <Control-A> IA5100 CSLD RATE TABLE
2. <Control-A> IA5200 CSLD RATE TEST
3. <Control-A> IA5300 CSLD VOLUME TABLE
4. <Control-A> IA5400 CSLD MOVING AVERAGE TABLE
5. <Control-A> I10100 SYSTEM STATUS REPORT
6. <Control-A> I10200 SYSTEM CONFIGURATION REPORT
7. <Control-A> I11100 PRIORITY ALARM HISTORY
8. <Control-A> I11200 NON-PRIORITY ALARM HISTORY
9. <Control-A> I20100 INVENTORY REPORT
10.<Control-A> I20200 DELIVERY REPORT
11.<Control-A> I20600 TANK ALARM HISTORY REPORT
12.<Control-A> I25100 CSLD RESULTS
13.<Control-A> I60900 SET TANK THERMAL EXPANSION COEFFICIENT
14.<Control-A> I61200 SET TANK MANIFOLDED PARTNERS
Is tank assigned to a pump sense input or assigned to a line leak device?
If assigned to a pump sense collect the following reports:
1. <Control-A> I77100 PUMP SENSE CONFIGURATION REPORT
2. <Control-A> I77200 PUMP SENSOR TANK ASSIGNMENT REPORT
3. <Control-A> I77300 PUMP SENSOR DISPENSE MODE REPORT
4. <Control-A> IB7100 PUMP SENSOR DIAGNOSTIC REPORT
OR - if assigned to PLLD collect the following report:
1. <Control-A> I78000 PRESSURE LINE LEAK GENERAL SETUP INQUIRY