CSLD Troubleshooting
CSLD Diagnostic Aids
Figure 11-3.
CSLD Rate Table Example
IA5100
MAR 14, 1996 8:12 AM
CSLD DIAGNOSTICS: RATE TABLE
T 1:SUPER
TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS VOL INTVL DEL ULLG EVAP
9602202227 0 -0.016 39.2 38.3 36.3 0.02 191 4281 174.5 2.7 168 0.000
9602210128 0 0.016 39.3 38.2 35.9 0.02 169 4281 174.5 5.7 168 0.000
9602210428 0 -0.022 39.4 38.2 35.6 0.03 162 4281 57.5 8.7 168 0.000
9602210636 1 0.106 39.5 38.3 35.8 0.02 213 4207 19.5 10.8 172 0.000
9602210718 1 0.118 39.5 38.4 35.9 0.00 215 4175 19.5 11.5 173 0.000
9602212259 3 0.007 40.2 39.0 37.1 0.02 460 3557 174.5 27.2 204 0.000
TIME Test start time. (YYMMDDHHMM)
ST Test qualification status at last evaluation.
0 Test valid
1 Test rejected - duration too short.
2 Test rejected - start time too close to a delivery.
3 Test rejected - excessive dispensing prior to test.
4 Test rejected - excessive temperature change during test.
6 Test rejected - leak rate outlier.
LRT Leak rate in gph (negative number = a loss, no sign = a gain)
AVTMP Average fuel temperature
TPTMP Temperature of top thermistor in the tank.
BDTMP Temperature of thermistor on the board.
TMRT Rate of temperature change during the test.
DSPNS Factor related to the amount of dispensing prior to the test.
VOL Volume at the start of the test.
INTVL Test Duration in minutes.
DEL Time since the last delivery in hours.
ULLG Amount of surface area of the tank that is not covered by fluid.
EVAP
If the Reid Vapor Pressure table has been entered, the evaporation rate will
be here.
----- Partial set of entries shown ------