Dual-Float Discriminating Sensor Alarms
MMM DD, YYYY HH:MM XM
L1: HIGH LIQUID ALARM
MMM DD, YYYY HH:MM XM
L1: FUEL ALARM
(Flashing Red light)
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
L1: SENSOR OUT ALARM
MMM DD, YYYY HH:MM XM
L1: LIQUID ALARM
(Flashing Yellow light)
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
L1: SHORT ALARM
ALARM
TEST
ALARM
TEST
CAUSE:
The sensor at the location shown has
detected fuel vapor or liquid.
ACTION:
Investigate the cause of the alarm and
take appropriate action.
CAUSE:
The sensor at the location shown has
detected at least 8 inches (20.3 cm) of
non-hydrocarbon liquid.
ACTION:
Call for service following the procedures
established for your site.
CAUSE:
The sensor at the location shown has
detected at least 1 inch (25 mm) of
non-hydrocarbon liquid.
ACTION:
Call for service following the proce-
dures established for your site.
CAUSE:
The sensor at the location shown has
been disconnected or is inoperative.
ACTION:
Call for service following the proce-
dures established for your site.