Hourly Recon Monitoring (HRM) Alarms -
International Only
(Flashing Red light)
(Flashing Yellow light)
DD-MM-YY HH:MM XM
T1: RECON WARNING
DD-MM-YY HH:MM XM
T1: RECON ALARM
ALARM
TEST
ALARM
TEST
CAUSE:
The difference between the volume of fuel dis-
pensed and the volume of fuel drawn from the tank
has exceeded the Reconciliation Warning Threshold.
ACTION:
Investigate the cause of the alarm and follow the site
procedure for wetstock variances.
CAUSE:
The difference between the volume of fuel dispensed
and the volume of fuel drawn from the tank has
exceeded the Reconciliation Alarm Threshold.
ACTION:
Investigate the cause of the alarm and follow the site
procedure for wetstock variances.
NOTE:
Pump testing or repairs involving dispensing
fuel that is subsequently returned to a tank will
cause a Reconciliation warning or alarm.
Check for this or a similar cause before carrying
out wetstock variance procedures. Reconcilia-
tion warnings or alarms caused in this manner
will clear.
See also Hourly Recon Monitoring (page 4).