T1: SUDDEN LOSS ALARM
MMM DD, YYYY HH:MM XM
T1: HIGH PRODUCT ALARM
(Flashing Yellow light)
(Flashing Red light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
T1: MAX PRODUCT ALARM
(Flashing Red light)
MMM DD, YYYY HH:MM XM
T1: PROBE OUT ALARM
(Flashing Red light)
ALARM
TEST
ALARM
TEST
CAUSE:
Fuel loss in the tank has exceeded a
pre-set limit during a Leak Test. This
indicates a possible leak, fuel being dis-
pensed or other unauthorized loss.
ACTION:
Check that fuel has not been dispensed
from the tank during the test period. Call
for service following the procedures
established for your site.
CAUSE:
Fuel level in the tank has exceeded the
High Product Alarm limit.
ACTION:
Stop the delivery immediately!
CAUSE:
Fuel level in the tank has exceeded
the Safe Working Capacity.
ACTION:
Stop the delivery immediately!
CAUSE:
There is a fault with the sensing probe
in the tank.
ACTION:
Call for service following the proce-
dures established for your site.