Page
17
In-Tank Alarms
(Continued)
(Flashing Red light)
(Flashing Red light)
MMM DD, YYYY HH:MM XM
T1: PER TST NEEDED ALM
MMM DD, YYYY HH:MM XM
T1: PERIODIC TEST FAIL
ALARM
TEST
ALARM
TEST
(Flashing Red light)
(Flashing Red light)
MMM DD, YYYY HH:MM XM
T1: ANN TST NEEDED ALM
MMM DD, YYYY HH:MM XM
T1: ANNUAL TEST FAIL
ALARM
TEST
ALARM
TEST
CAUSE:
A periodic in-tank leak test has not been
successfully completed within the pre-
set time period.
ACTION:
Schedule a 0.2 gph (0.76 lph) test.
CAUSE:
An annual in-tank leak test has not
been successfully completed within
the preset time period.
ACTION:
Schedule a 0.1 gph (0.38 lph) test.
CAUSE:
In-tank leak periodic (0.2 gph [0.76 lph])
test failed.
ACTION:
Rerun in-tank leak test. If second test
fails, call for service following the proce-
dures established for your site.
CAUSE:
In-tank leak annual (0.1 gph [0.38
lph]) test failed.
ACTION:
Rerun in-tank leak test. If second
test fails, call for service following
the procedures established for your
site.