Page
14
In-Tank Alarms
MMM DD, YYYY HH:MM XM
T1: HIGH WATER WARNING
(Flashing Yellow light)
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
T1: INVALID FUEL LEVEL
ALARM
TEST
ALARM
TEST
CAUSE:
Water collecting in the tank has exceed-
ed the Water Warning level.
ACTION:
Close all pumps attached to this tank.
Call for service following the procedures
established for your site.
CAUSE:
Fuel level in the tank is below the Deliv-
ery Needed level.
ACTION:
Arrange a delivery.
CAUSE:
Fuel and water level floats on the probe
are too close together due to a lack of
fuel in the tank.
ACTION:
Arrange a delivery.
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
T1: TANK TEST ACTIVE
MMM DD, YYYY HH:MM XM
T1: DELIVERY NEEDED
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
CAUSE:
If enabled, the system will display this
message when a tank test is in prog-
ress.
ACTION:
Do not deliver to or dispense from the
tank being tested.