Appendix B
Interface To BACnet & Modbus Tables
B-4
Table B-10.
MAG Sensor Veeder-Root Interface To BACnet And Modbus
Table B-11.
Smart Sensor Veeder-Root Interface To BACnet And Modbus
Table B-12.
PLLD Veeder-Root Interface To BACnet And Modbus
Point Name
BACnet Object Type
BACnet Object ID
Modbus Register
MAG Sensor X Setup Data Warninq
BI
X001
10X01
MAG Sensor X Communication Alarm
BI
X002
10X02
MAG Sensor X Fault Alarm
BI
X003
10X03
MAG Sensor X Fuel Warning
BI
X004
10X04
MAG Sensor X Fuel Alarm
BI
X005
10X05
MAG Sensor X Water Warning
BI
X006
10X06
MAG Sensor X Water Alarm
BI
X007
10X07
MAG Sensor X High Liquid Warning
BI
X008
10X08
MAG Sensor X High Liquid Alarm
BI
X009
10X09
MAG Sensor X Low Liquid Warning
BI
X010
10X10
MAG Sensor X Low Liquid Alarm
BI
X011
10X11
MAG Sensor X Temperature Warning
BI
X012
10X12
MAG Sensor X Relay Active
BI
X013
10X13
MAG Sensor X Install Alarm
BI
X014
10X14
Point Name
BACnet Object Type
BACnet Object ID
Modbus Register
Smart Sensor X Setup Data Warninq
BI
X001
10X01
Smart Sensor X Communication Alarm
BI
X002
10X02
Smart Sensor X Fault Alarm
BI
X003
10X03
Smart Sensor X Fuel Warning
BI
X004
10X04
Smart Sensor X Fuel Alarm
BI
X005
10X05
Smart Sensor X Water Warning
BI
X006
10X06
Smart Sensor X Water Alarm
BI
X007
10X07
Smart Sensor X High Liquid Warning
BI
X008
10X08
Smart Sensor X High Liquid Alarm
BI
X009
10X09
Smart Sensor X Low Liquid Warning
BI
X010
10X10
Smart Sensor X Low Liquid Alarm
BI
X011
10X11
Smart Sensor X Temperature Warning
BI
X012
10X12
Smart Sensor X Relay Active
X013
10X13
Smart Sensor X Install Alarm
X014
10X14
Smart Sensor X Fault Warning
X015
10X15
Smart Sensor X Vacuum Warning
X016
10X16
Smart Sensor X No Vacuum Warning
X017
10X17
Point Name
BACnet Object Type
BACnet Object ID
Modbus Register
PLLD X Setup Data Warninq
BI
X001
10X01
PLLD X Gross Test Fail Alarm
BI
X002
10X02
PLLD X Annual Test Fail Alarm
BI
X003
10X03
PLLD X Periodic Test Needed Warning
BI
X004
10X04
PLLD X Periodic Test Needed Alarm
BI
X005
10X05
PLLD X Sensor Open Alarm
BI
X006
10X06
PLLD X High Pressure Alarm
BI
X007
10X07
PLLD X Shutdown Alarm
BI
X008
10X08
PLLD X High Pressure Warning
BI
X009
10X09
PLLD X Continuous Handle On Warning
BI
X010
10X10
PLLD X Periodic Test Fail Alarm
BI
X011
10X11
PLLD X Annual Test Needed Warning
BI
X012
10X12
PLLD X Annual Test Needed Alarm
BI
X013
10X13
PLLD X Low Pressure Alarm
BI
X014
10X14
PLLD X Sensor Short Alarm
BI
X015
10X15
PLLD X Continuous Handle On Alarm
BI
X016
10X16
PLLD X Fuel Out Alarm
BI
X017
10X17
PLLD X Line Equipment Alarm
BI
X018
10X18
PLLD X Gross Test Needed Alarm
BI
X019
10X19