Setup For QuickServer
Input COM Settings on the device connected to the QuickServer
6
Input COM Settings on the device connected to the QuickServer
•
The connected serial device MUST have the same baud rate, data bits, stop bits, and parity settings as the
QuickServer.
•
To set the QuickServer’s COM settings, See “Connecting to QuickServer Web Configurator” on page 13.
•
Table 3 specifies the device serial port settings required to communicate with the QuickServer.
Selecting The Desired Protocol Configuration
QuickServer ProtoNode units use the ‘S’ bank of DIP switches (S0 - S3) to select the protocol configuration (see
Figure 2).
Figure 2. QuickServer S Bank (Profile Selections) DIP Switches
See Table 4 for the S Bank DIP switch settings.
Table 3. COM Settings
Port Setting
TLS-3XX/TLS4XX
Protocol
V-R Interface
Baud Rate
9600
Parity
Odd
Data Bits
7
Stop Bits
1
Table 4. Profile Settings For QuickServer
QuickServer ProtoNode
S Bank DIP Switches
Profile
S0
S1
S2
S3
BACnet/IP
Off
Off
Off
Off
BACnet MS/TP
On
Off
Off
Off
2
3
S0
S1
S2
S3
Off
On
S0 - S3 DIP Switches
Bank DIP Switch Location
When setting DIP switches,
ensure that power to the
board is OFF.
NOTICE