7
Setup For QuickServer
BMS Network Settings: MAC Address Node-ID And Baud Rate
BMS Network Settings: MAC Address Node-ID And Baud Rate
BACNET MS/TP: SETTING THE MAC ADDRESS FOR BMS NETWORK
•
Only 1 MAC Address is set for QuickServer regardless of how many devices are connected to QuickServer.
•
Set the BACnet MS/TP MAC Address of the QuickServer to a value between 1 to 127 (Master MAC Address);
this is so that the BMS front end can find QuickServer via BACnet Auto-Discovery.
Never set a BACnet MS/TP MAC Address of the QuickServer to a value from 128 to 255.
Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS front
ends that support Auto-Discovery of BACnet MS/TP devices.
•
Set “A” bank DIP switches A0 – A7 to assign a MAC Address to the QuickServer for BACnet MS/TP (see
Figure 3).
Figure 3. QuickServer A Bank DIP Switches
•
Refer to Appendix C for the complete range of MAC Addresses and DIP switch settings.
MODBUS RTU AND MODBUS TCP/IP: SETTING THE NODE-ID
•
The Modbus RTU and Modbus TCP/IP Node-IDs are assigned by setting the A-bank dip switches. (see
Figure 3).
•
Node-ID’s range from 1-255. Refer to Appendix C for the full range of addresses for setting Node-ID.
Modbus TCP/IP and Mod-
bus RTU
Off
On
Off
Off
Table 4. Profile Settings For QuickServer (Continued)
QuickServer ProtoNode
S Bank DIP Switches
Profile
S0
S1
S2
S3
4
NOTICE
A0 - A7 DIP Switches
Bank DIP Switch Location
A0
A1
A2
A3
A4
A5
A6
A7
Off
On
When setting DIP switches,
ensure that power to the
board is OFF.
NOTICE
5