INSTALLATION
Series 655
68/112
Edition 23.09.2019
979645EA
Command
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
Description
UPLOAD
LEARN DATA
50
48
1
-
3,11
X,XY
X: Index (3 byte, range 000 .. 103, ASCII coded)
Y: Data (8 byte)
This command loads the learn data sets from the valve up to the host.
There are a total number of 104 data sets which need to be uploaded separately.
Example:
Send : “000”
48 48 48
Response: “00000754241”
48 48 48 48 48 55 53 52 50 52 49
DOWNLOAD
LEARN DATA
51
48
1
-
11,3
XY,X
X: Index (3 byte, range 000 .. 103, ASCII coded)
Y: Data (8 byte)
This command loads the learn data sets from host down to the valve.
There are a total number of 104 data sets which need to be downloaded separately.
Example:
Send: “00000754241”
48 48 48 48 48 55 53 52 50 52 49
Response: “000”
48 48 48
4.10.9
S-Analog Sensor Object (Class ID 49)
Models the acquisition of a reading from a physical sensor in a device
Command
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
Description
DATA TYPE
Set
16
49
1
3
1
X
Get
14
X:
195
signed integer
202
floating point
This command defines the data type for all pressure and position values.
Default value is 195.
PESSURE
POSITON
READING
Get
14
49
1 Pressure
3 Position
6
2 integer
4 float
X
X:
Instance 1 pressure
Nominal range pressure is 0 … 10’000 but it may be scaled.
Refer also to command GAIN and picture on the following page for details.
X:
Instance 3 position
Nominal range is 0 (closed) … 10’000 (open).
Refer also to command GAIN and picture on the following page for details.