INSTALLATION
Series 642
20/113
Edition 2017-11-24
605593EC
4.4
Admissible forces
NOTICE
Force at flange and valve body
Forces from evacuating the system, from the weight of other components, and from
baking can lead to deformation and malfunctioning of the valve.
Do not higher force the valve body as specified.
The following forces are admissible.
DN (nom. I.D.)
Axial traction or
pressure force «F
A
»
Bending moment «M»
F
A
mm
inch
N
lbf
Nm
lbf . ft
63
2½
1960
440
78
58
80
3
1960
440
78
58
100
4
2450
560
98
72
160
6
2940
660
147
108
200
8
2940
660
147
108
250
10
3430
770
196
145
320
12
3920
880
294
217
350
14
3920
880
294
217
400
16
7840
1760
980
722
In case of both kind of forces are occurring («FA» und «M»), the above shown
values are invalid. Please contact VAT in this case.