INSTALLATION
Series 642
60/113
Edition 2017-11-24
605593EC
4.8.2.2
Input assembly
Instance
Type
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
3
Input
1
EXCEPTION STATUS
2
PRESSURE low byte
3
PRESSURE high byte
4
POSITION low byte
5
POSITION high byte
EXCEPTION STATUS will respond with one out of below selections, see also «Explicit messaging inquiry
commands».
Description
Value
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Manufacturer specific alarm
present
84h
1
0
0
0
0
1
0
0
Manufacturer specific warning
present
C0h
1
1
0
0
0
0
0
0
No warning, no error present
80h
1
0
0
0
0
0
0
0
PRESSURE will respond with any value between the lowest and the highest value, see also «Explicit
messaging inquiry commands»:
Description
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Lowest value
0
0000h
low byte
00h
0
0
0
0
0
0
0
0
high byte
00h
0
0
0
0
0
0
0
0
Highest value
10000
2710h
low byte
10h
0
0
0
1
0
0
0
0
high byte
27h
0
0
1
0
0
1
1
1
POSITION will respond with any value between the lowest and the highest value, see also «Explicit
messaging inquiry commands»:
Description
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Lowest value
0
0000h
low byte
00h
0
0
0
0
0
0
0
0
high byte
00h
0
0
0
0
0
0
0
0
Highest value
10000
2710h
low byte
10h
0
0
0
1
0
0
0
0
high byte
27h
0
0
1
0
0
1
1
1