HIGH TEMPERATURE ALARM
This function establishes the temperature
difference
above the main set point that the
room can reach before a high temperature
alarm is signaled. When a high temperature
alarm occurs, an alarm contact is activated
and the alarm LED lights up on the MST.
The high temperature alarm is adjusted in 0.5
degree increments from a minimum setting of
0°F (0°C) to a maximum setting of 32.0°F
(18.0°C)
Adjusting the high temperature alarm:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjuster dial back and
forth to enter secondary function mode,
•
rotate the selector dial to position (11),
•
rotate the adjuster dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The high temperature alarm setting is
displayed on the MST-5.
Alarm
CHAPTER 3 - USER’S GUIDE