STAGE 3 RELATIVE SET POINT
The stage 3 relative set point establishes the
temperature above the main set point at which
stage 3 begins to operate. The value is a
temperature
difference
from the main set
point.
The stage 3 relative set point is adjusted in 0.5
degree increments from a minimum setting of
0.0°F (0.0°C) to a maximum setting of 32.0°F
(16.0°C).
Adjusting the relative set point of stage 3:
•
rotate the selector dial to position (4),
•
rotate the adjuster dial counterclockwise to
decrease the relative set point, and
clockwise to increase it.
The stage 3 relative set point is displayed on
the MST-5.
Example: A main set point of 70°F along
with a Stage 3 relative set point of 4°F is
selected. When the temperature of the
room reaches 74°F, Stage 3 begins to
operate.