Page 38
MST 5
LOW TEMPERATURE ALARM
This function establishes the temperature
difference
below the main set point that the
room can reach before a low temperature alarm
is signaled. When a low temperature alarm
occurs an alarm contact is activated and the
alarm LED lights on the MST.
The low temperature alarm is adjusted in 0.5
degree increments from a minimum setting of -
32.0°F (-18.0°C) to a maximum setting of 0.0°F
(0.0°C).
Adjusting the low temperature alarm
setting:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjuster dial back and
forth to enter secondary function mode,
•
rotate the selector dial to position (10),
•
rotate the adjuster dial counterclockwise to
decrease the setting, and clockwise to
increase it.
The low temperature alarm setting is displayed
on the MST-5.
Alarm
www.monitrol.com