STAGE 4 RELATIVE SET POINT
The stage 4 relative set point is the relative
temperature at which Heater/Fan of stage 4
begins to operate. This value is the
temperature
difference
from the main set
point.
When a heater is being controlled, the relative
set point is bellow the main set point. When a
fan is being controlled, the relative set point is
above the main set point.
The stage 4 relative set point temperature is
adjusted in 0.5 degree increments from a
minimum setting of -15.0°F (-10.0°C) to a
maximum setting of 32.0°F (16.0°C).
Adjusting the stage 4 relative temperature:
•
rotate the selector dial to position (5),
•
rotate the adjuster dial counterclockwise to
decrease the relative set point, and
clockwise to increase it.
The stage 4 relative set point is displayed
MST-5.
CHAPTER 3 - USER’S GUIDE
Example: The main set point temperature is adjusted to
70°F. A heater is in use and the relative set point is
adjusted to -2°F. When room temperature reaches 68°F
the heater begins to operate.
A fan is in use and the relative set point is adjusted to 6°
F. When room temperature reaches 76°F, stage 4 begins
to operate.
If a 2 speed motors is used, stage 3 shuts
off when stage 4 begins to operate.
www.monitrol.com
Содержание MST-5
Страница 8: ...Page 8 MST 5 www monitrol com ...
Страница 16: ...Page 16 MST 5 Fig 5 Main bottom Board terminal blocks and ground connection www monitrol com ...
Страница 17: ...Page 17 CHAPTER 3 USER S GUIDE CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 18: ...Page 18 MST 5 www monitrol com ...
Страница 44: ...MAV MST 5M Ver 1 1 October 1995 Rev July 1997 Rev June 2001 www monitrol com ...