Page 34
MST 5
DRIP COOL DUTY CYCLE
As long as the actual temperature is below the
main set point, the drip cool unit will not
operate. When room temperature rises above
the stage 3 relative set point, configured by
primary function (4), the drip cool units begins
to operate in a duty cycle mode. The duty
cycle sets the percentage of time the drip cool
unit is ON versus the percentage of time the
unit is OFF. The ON time is entered as a
percentage of a
12 minutes
period. If a fan is
used, set this value at 100%.
Adjusting the duty cycle setting:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjuster dial back and
forth to enter secondary function mode,
•
rotate the selector dial to position (4),
•
rotate the adjuster dial counterclockwise to
decrease the duty cycle setting, and
clockwise to increase it.
The duty cycle setting is displayed on the
MST-5.
Timer
Example: The duty cycle is set to 25%. When room
temperature rises above the relative set point the drip
cool units operates for 3 minutes, and go OFF for 9
minutes.