Page 40
MST 5
SYMPTOM
CAUSE and REMEDY
Lo is
continually
displayed
−
Temperature is below minimum (13.5
°
F
or -10.0
°
C).
−
Probe is disconnected or defective.
Hi is
continually
displayed
−
Temperature is above maximum
(105.0°F or 41°C).
−
Probe is short circuited.
Fan(s) or
heater not
operating
−
Verify whether the fan LED is on. If
LED is on yet fan or heater is not
operating, verify wiring, and fan or
heater.
Stage 4 and
5. Fan or
Heater is
operating
erratically
−
Verify that the function on position 5
and 6 in secondary mode is correctly
adjusted.
−
Verify the minimum rating (10mA at
115V or 20mA at 230V.
Display is
blank
−
Verify that the line voltage selector
switch is properly set.
−
Verify that the 10 pin flat cable
between the main board and the
faceplate board is connected.
TROUBLESHOOTING
Storage
Temperature: -4 to 130°F (-20 to 55°C)
Operation
temperature: 32 to 122°F (0 to 50°C)
Weight: 5 pounds (2.25Kg)
Dimension: 8.35”x4.60”x7.87” (212x117x200mm)
www.monitrol.com