Page 29
RAMPING
The ramping function automatically reduces
the main set point by the set value every 24
hours.
The ramping setting is adjusted in 0.01 degree
decrements from a minimum setting of OFF, -
0.01°F (-0.01°C) to a maximum setting of -
0.99°F (-0.50°C).
The main set point must be greater than
the limit
.
Adjusting ramping:
•
rotate the selector dial to position (9),
•
rotate the adjuster dial counterclockwise to
increase the ramping rate, and clockwise
to decrease it.
The ramping setting is displayed on the MST-
5.
NOTE: When ramping is activated, the main set point
temperature cannot be manually adjusted.
Ramping automatically shuts OFF when the minimum
temperature limit is reached!
Example: The main set point temperature is set to 70°F
and ramping is adjusted to -0.05°F. The following day the
main set point temperature drops to 69.95°F followed by
69.90°F on the next day. Although the main set point real
value decreases, the display will be changed after 10
days. The main set point will then be 69.5°F.
CHAPTER 3 - USER’S GUIDE
www.monitrol.com
Содержание MST-5
Страница 8: ...Page 8 MST 5 www monitrol com ...
Страница 16: ...Page 16 MST 5 Fig 5 Main bottom Board terminal blocks and ground connection www monitrol com ...
Страница 17: ...Page 17 CHAPTER 3 USER S GUIDE CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 18: ...Page 18 MST 5 www monitrol com ...
Страница 44: ...MAV MST 5M Ver 1 1 October 1995 Rev July 1997 Rev June 2001 www monitrol com ...