DIP-1C USER’S GUIDE
DIP-1C Section
C-23
Normal Mode Settings
Winter Minimum Position (POS 1)
These parameters will only appear if the outside temperature is used on at
least one of the units connected to the DIP-1C.
Winter Minimum Position
This parameter is used to adjust the minimum opening position when the
Outside Temperature
is equal to or below
Winter Temp
. When the
Outside Temperature
is between
Winter Temp
and
Summer
Temp
, the
minimum opening position will modulate accordingly. The calculated
minimum opening is displayed at the unit 1
Variable 1 Start Position
parameter. This parameter is adjusted in 1% increments from 0% to 100%.
Winter Temp
This parameter is used to set the temperature at which minimum opening
position will be equal to
Winter Minimum Position
. When the
Outside
Temperature
is between
Winter Temp
and
Summer
Temp
, the minimum
opening position will modulate accordingly. The calculated minimum
opening is displayed at the unit 1
Variable 1 Start Position
parameter. This
parameter is adjusted in 0.1° increments from -58.0°F to 140.0°F (-50.0°C
to 60.0°C).
Summer Minimum Position (POS 2)
These parameters will only appear if the outside temperature is used on at
least one of the units connected to the DIP-1C.
Summer Minimum Position
This parameter is used to adjust the minimum opening position when the
Outside Temperature
is equal to or above
Summer Temp
. When the
Outside Temperature
is between
Summer Temp
and
Winter
Temp
, the
minimum opening position will modulate accordingly. The calculated
minimum opening is displayed at the unit 1
Variable 1 Start Position
parameter. This parameter is adjusted in 1% increments from 0% to 100%.
Summer Temp
This parameter is used to set the temperature at which minimum opening
position will be equal to
Summer Minimum Position
. When the
Outside
Temperature
is between
Summer Temp
and
Winter
Temp
, the minimum
opening position will modulate accordingly. The calculated minimum
opening is displayed at the unit 1
Variable 1 Start Position
parameter. This
parameter is adjusted in 0.1° increments from -58.0°F to 140.0°F (-50.0°C
to 60.0°C).
www.monitrol.com
Содержание DIP-1C
Страница 3: ...DIP 1C WIRING DIAGRAM DIP 1C Section A 3 WIRING DIAGRAM DIP 1C SECTION A www monitrol com ...
Страница 7: ...DIP 1C INSTALLATION DIP 1C Section B 7 INSTALLATION DIP 1C SECTION B www monitrol com ...
Страница 18: ...DIP 1C USER S GUIDE Section C 18 DIP 1C USER S GUIDE DIP 1C SECTION C www monitrol com ...
Страница 37: ...DIP 1C INDEX WARRANTY DIP 1C Section D 37 INDEX WARRANTY DIP 1C SECTION D www monitrol com ...
Страница 41: ...www monitrol com ...
Страница 42: ...DIP 1C_EN VER 1 1 August 12 2014 www monitrol com ...