DIP-1C WIRING DIAGRAM
Section A-6
DIP-1C
DIP-1C
Electrician’s notes
(COMMUNICATION WIRING) SHIELDED LOW CAPACITANCE WIRE,
(Capacitance between conductors @ 1Khz = 24pF/ft), TWISTED PAIR (8
twist/ft), AWG #22, 820ft (250m) MAX LENGTH. (Ex.: BELDEN 8761)
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING
CODE.
INSTALL LOW VOLTAGE WIRES (POTENTIOMETER OR COMPUTER LINK
WIRES) AT LEAST 12in. (30cm) AWAY FROM HIGH VOLTAGE WIRES
(120/230VAC, 24VDC). ALWAYS CROSS HIGH AND LOW VOLTAGE WIRES
AT A 90-DEGREE ANGLE.
RELAYS: 10A @ 240VAC RESISTIVE, MOTOR 1HP @ 240VAC, 1/2HP @
120VAC AT EACH OUTPUT.
MAXIMUM 2 WIRES OF SAME SIZE PER BLACK TERMINAL, NO BIGGER
THAN AWG #12, NO SMALLER THAN AWG #22.
1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF YOU
WANT TO CONNECT MORE THAN 1 WIRE, NO BIGGER THAN AWG #12,
NO SMALLER THAN AWG #28.
CHECK INSTALLATION GUIDE FOR ALARM WIRING.
USE SHIELD FOR SHIELDING PURPOSE ONLY. CONNECT THE SHIELD TO
GROUND PLATE
. NEVER LEAVE THE SHIELD UNCONNECTED AT BOTH
ENDS. NEVER CONNECT BOTH ENDS OF THE SHIELD TO GROUND
PLATE
. THE USE OF A SHIELD FOR POTENTIOMETER AND ALL
COMMUNICATION WIRE IS
MANDATORY
.
1
5
7
8
4
1
2
3
6
www.monitrol.com
Содержание DIP-1C
Страница 3: ...DIP 1C WIRING DIAGRAM DIP 1C Section A 3 WIRING DIAGRAM DIP 1C SECTION A www monitrol com ...
Страница 7: ...DIP 1C INSTALLATION DIP 1C Section B 7 INSTALLATION DIP 1C SECTION B www monitrol com ...
Страница 18: ...DIP 1C USER S GUIDE Section C 18 DIP 1C USER S GUIDE DIP 1C SECTION C www monitrol com ...
Страница 37: ...DIP 1C INDEX WARRANTY DIP 1C Section D 37 INDEX WARRANTY DIP 1C SECTION D www monitrol com ...
Страница 41: ...www monitrol com ...
Страница 42: ...DIP 1C_EN VER 1 1 August 12 2014 www monitrol com ...