DIP-1C USER’S GUIDE
Section C-30
DIP-1C
System Mode Settings
(POS 7)
No Stage Position Summer
NOStS
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the
Outside Temperature
is equal to
or above
Summer Temp
. When the
Outside Temperature
is lower than
Summer Temp
, but greater than
Winter Temp
, the position the inlet will
take when no ventilation stages are activated will modulate according to this
setting and
No Stage Position Winter
. This parameter will appear only if at
least one of the units connected to the DIP-1C uses an outside temperature
probe. This parameter is adjusted in 1% increments from 0% to 100%.
No Stage Position
NOStg
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the
Outside Temperature
is not used.
This parameter will appear only if none of the units connected to the DIP-1C
use an outside temperature probe. This parameter is adjusted in 1%
increments from 0% to 100%.
No Stage Position Winter
NOStW
This parameter is used to set the position the inlet will take when no
ventilation stages are activated and the
Outside Temperature
is equal to
or below
Winter Temp
. When the
Outside Temperature
is lower than
Summer Temp
, but greater than
Winter Temp
, the position the inlet will
take when no ventilation stages are activated will modulate according to this
setting and
No Stage Position Summer
. This parameter will appear only if
at least one of the units connected to the DIP-1C uses an outside
temperature probe. This parameter is adjusted in 1% increments from 0% to
100%.
(POS 8)
Inlet Alarm Option
ALOPT
This parameter is used to determine if the alarm relay will activate when the
inlet’s potentiometer is defective. If this parameter is set to
ON
, the
alarm relay will activate when the inlet’s potentiometer is defective. If this
parameter is set to
OFF
, the alarm relay will not activate when the inlet’s
potentiometer is defective.
(POS 9)
Display Language
LANG
This parameter is used to select the language used by the DIP-1C. If this
parameter is set to
ENG
, the configuration will use the English language.
If this parameter is set to
FrA
, the configuration will use the French
language.
www.monitrol.com
Содержание DIP-1C
Страница 3: ...DIP 1C WIRING DIAGRAM DIP 1C Section A 3 WIRING DIAGRAM DIP 1C SECTION A www monitrol com ...
Страница 7: ...DIP 1C INSTALLATION DIP 1C Section B 7 INSTALLATION DIP 1C SECTION B www monitrol com ...
Страница 18: ...DIP 1C USER S GUIDE Section C 18 DIP 1C USER S GUIDE DIP 1C SECTION C www monitrol com ...
Страница 37: ...DIP 1C INDEX WARRANTY DIP 1C Section D 37 INDEX WARRANTY DIP 1C SECTION D www monitrol com ...
Страница 41: ...www monitrol com ...
Страница 42: ...DIP 1C_EN VER 1 1 August 12 2014 www monitrol com ...