Page 33
WINTER TEMPERATURE
This function sets the temperature for winter,
which is adjusted in 0.5 degree increments
from a minimum setting of -3.5ºF (-19.0ºC) to a
maximum setting of 99.5ºF (39.5ºC). When the
exterior temperature is between the winter and
summer temperature, and none of the
ventilation stages are activated, the air inlet
varies proportionally between the Summer
minimum position and the Winter minimum
position.
Setting the winter position:
•
set the Selector to position (12)
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
set the Selector dial to position (1),
•
rotate the Adjustor dial counterclockwise to
decrease the winter position, and clockwise
to increase it.
The winter temperature is displayed on the
DIP-1/115.
Example: The minimum winter position set by primary
function (1) is adjusted to 10%, and the winter
temperature is set to 20ºF. When the exterior
temperature reaches 20ºF and none of the ventilation
stages are activated, the air inlet opens at 10%.
TEMP.
CHAPTER 3 - USER’S GUIDE
www.monitrol.com