Page 38
DIP-1/115
END POSITION FOR THE SECOND STAGE
(UNIT 2)
The end position for the second stage (unit 2)
sets the air inlet position when second stage
(unit 2) runs at maximum speed.
The air inlet varies proportionally between the
start and the end position at the same time the
fan accelerates.
Adjusting the end position for the second
stage (unit 2):
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (6),
•
rotate the Adjustor dial counterclockwise to
decrease the end position for the second
stage (unit 2), and clockwise to increase it.
The end position for the second stage (unit 2)
is displayed on the DIP-1/115, and is adjusted
in opening percentage (0-100%).
Example: The end position for the second stage (unit 2)
is set to 72%. When the second stage (unit 2) runs at
maximum speed the air inlet opens at 72%.
2nd UNIT
www.monitrol.com