Page 37
START POSITION FOR THE SECOND STAGE
(UNIT 2)
The start position for the second stage (unit 2)
sets the air inlet position when the second
stage (unit 2) begins to operate at minimum
speed.
Adjusting the start position for the second
stage (unit 2):
•
set the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
set the Selector to position (5),
•
rotate the Adjustor dial counterclockwise to
decrease the start position for the second
stage (unit 2), and clockwise to increase it.
The start position for the second stage (unit 2)
is displayed on the DIP-1/115, and is adjusted
in opening percentage (0-100%).
Example: The start position for the second stage (unit 2)
is set to 65%. When the second stage begins to operate
at minimum speed, the air inlet opens at 65%.
2nd UNIT
CHAPTER 3 - USER’S GUIDE
www.monitrol.com