VANNER POWER GROUP
VANNER POWER GROUP
IQ SERIES
IQ SERIES
- 34 -
IQ SERIES OWNERS MANUAL
Symptom
BATTERY LOW lamp illuminates when AC load is applied.
Solution
Check battery connections.
Check battery condition.
Recharge battery if voltage is less than 10.5 VDC.
Check the charging system for proper operation (vehicle alternator, PV array, generator).
Symptom
OVERTEMP lamp illuminates.
Solution
Something has caused the unit to overheat. Check for obstruction of air flow to the cooling fan or
from ventilation holes. Verify AC load is within unit's rated capacity.
Symptom
OVERLOAD lamp illuminates with AC load applied.
Solution
Verify AC load is within unit's rated capacity.
Symptom
DC fuse blows when connecting DC input cables.
Solution
Check for reverse polarity: red cable to battery positive (+), black cable to battery negative (-) The
unit may be damaged and require repair service.
Symptom
Excessive audible buzzing during inverter operation but inverter operates loads.
Solution
Check mounting bracket bolt tightness
Remount inverter with rubber insulator washers
Symptom
AC loads do not seem to be fully energized when operating from inverter power
Solution
Check AC output voltage at convenience receptacle.
Check for overheated DC or AC wiring
Symptom
Unit does not operate and a “burnt wire” smell emits from inverter
Solution
Disconnect AC loads and battery immediately
Unit may require service
Содержание IQ12-2600
Страница 1: ...VANNER POWER GROUP VANNER POWER GROUP IQ SERIES IQ SERIES IQ SERIES OWNERS MANUAL 1...
Страница 2: ...VANNER POWER GROUP VANNER POWER GROUP IQ SERIES IQ SERIES 2 IQ SERIES OWNERS MANUAL...
Страница 43: ...VANNER POWER GROUP VANNER POWER GROUP IQ SERIES IQ SERIES IQ SERIES OWNERS MANUAL 43...
Страница 44: ...VANNER POWER GROUP VANNER POWER GROUP IQ SERIES IQ SERIES 44 IQ SERIES OWNERS MANUAL...