136 bright blue Installation Manual
Configuration
The VRI-2 will be connected to the
bright blue
via RS-485 protocol. A maximum of 16
reader interfaces
can be
connected to one
bright blue
data channel. Wire runs are limited to 4,000 feet (Data Only) from the
bright blue
to a VRI-2 (
see Recommended Wire Chart
). Data communication between the
bright blue
and the reader
interfaces can be a multiplex or a daisy chain configuration.
Multiplex configuration
In a multiplex configuration, each VRI-2 board is connected to any one of the Device connectors (Device 1-1
through 2-16) on the
bright blue
controller with TB6 for RS-485 communications and TB7 for power on a VRI-2 in
parallel. A maximum of 32
reader interfaces
(
16 VRI-2 boards if using both reader interfaces
) can be connected
in this manner (8 VRI-2 per
bright blue
data channel).
Note:
Only identical protocol devices can be connected on the same channel on the
bright blue
. VRI-2 devices
cannot be wired on the same data channel with any older Vanderbilt or Schlage devices.
Daisy chain configuration
In a daisy chain configuration, the VRI-2 reader interfaces are connected to one another in series. A maximum of
32 reader interfaces (
16 VRI-2 boards if using both reader interfaces
) can be connected to a
bright blue
(8 VRI-2
per
bright blue
data channel). This configuration is not recommended by Vanderbilt; if a wire is broken in the
loop, downstream devices will not communicate with
bright blue
.
PIN Functions
TB7 - Power source
Provides power to the VRI-2 from the
bright blue
.
▪
PIN 1 is Power (VIN), 12
– 24 VDC
▪
PIN 2 unused
▪
PIN 3 is Ground (GND)