VBBIM09/33/20 v5.0.3
Chapter 5 VBB-NRI
75
Environmental conditions
▪
Ambient Temperature: 0º to 49º C or 32º to 120º F
▪
The room must be dust free and clean.
▪
It is optimal to mount the enclosure on fire rated plywood which is affixed to a cinder block wall or a wall
covering i.e. sheetrock
▪
Mount the cabinet in a secure, but generally accessible location
Mounting
▪
Field Wiring - It is necessary to punch the knockouts in the metal enclosure for field wiring. It is
recommended that this is done before mounting the enclosure to the wall.
▪
A non-metallic sleeve is recommended to protect the wiring where it enters the cabinet.
▪
Mount the enclosure to the wall using the provided mounting holes. Recommended mounting hardware:
Four 1/4” x 1” lag bolts.
▪
To secure the VBB-NRI enclosure use two screws through the openings provided on the cover. Alternately
a lock can be added using the provided punch out section on the cover.
VBB-NRI IP Configuration
The IP address of the VBB-NRI has to be configured so that it can communicate with
bright blue
. Configuration
should occur after the reader interface is fully installed. There are two methods to configure the IP address: Static
IP and DHCP which are detailed below.
Note:
Communication is at 10Base-T
Static IP Configuration (Recommended)
1
Connect a PC with a web browser to the VBB-NRI.
▪
Direct Connection - Using a cross-over cable, the reader interface can be connected directly to the
network card of the PC.
▪
Network Connection - Using a regular network cable, the reader interface can be connected to a hub or
switch that is on the same network as the PC.