• A clearance of 2" (50 mm) between the chimney and any combustible material is required.
This space must remain free, without insulation or other combustible material.The parts of the
chimney that pass into inhabited spaces must be enclosed in an enclosure.
• For installations where more than one chimney is located in the same non-chase or within the
same area, their terminations must be separated by at least 16" (410 mm) horizontally, and
18" (460 mm) vertically. This separation is to prevent smoke migrating from one chimney to
another.
CHIMNEY: 12" (305mm) MIN.
ABOVE FLASHING
CHEMINÉE: 12" (305mm) MIN.
AU-DESSUS DU SOLIN
FLASHING:
6" (152mm) MIN.
SOLIN:
6" (152mm) MIN.
CRÊTE
CHEMINÉE
RIDGE
CHIMNEY
Note: The chimney chase on the roof must be the same size as the flashing.
•
WARNING: IF THE CHIMNEY IS INSTALLED IN AN ENCLOSURE ABOVE THE ROOF, IT
MUST EXCEED THE TOP OF THE FLASHING CONE BY AT LEAST 12 INCHES (30 CM).
THE FLASHING MUST HAVE A MINIMUM HEIGHT OF 6 INCHES (15.25CM). THE TOP
OF THE ENCLOSURE MUST BE MADE OF NON-COMBUSTIBLE MATERIALS.
The top of the enclosure
made of non-combustible
materials.