Description of parameters
vacon • 51
24-hour s358 (0)40 837 1150 • Email: [email protected]
1557
Relay
output 5
inversion
(2.3.8.3)
See par. ID1540.
1558
AI3
signal
selection
(2.2.15)
Connect the AI3 signal to the analogue input of your choice with this parameter using the TTF
programming method. More information on the TTF method in Vacon All in One Application
manual.
1567
Relay
output 6
function
(2.3.9.2)
1568
Relay
output 6
inversion
(2.3.9.3)
See par. ID1540.
1569
Coolant inlet
pressure
supervision
(2.10.5)
If the system is equipped with a pressure sensor set value 1 for this parameter and 0 if no
sensor is installed.
1570
Coolant inlet pressure alarm limit
(2.10.4)
When the inlet pressure drops below the limit set with this parameter, a warning is instigated.
A pressure sensor must be installed in the system.
1572 DIN6
function
(2.2.3)
This parameter has 2 selections. The default value is 0.
0 Preset Speed 1
1 Fault reset
Contact closed: All faults reset
1573
Relay output 6, signal selection
(2.3.9.1)
See par. ID1549.
1590
DIN2
input
(2.2.1)
This parameter changes the default status of the digital input.
0 = Digital input 'normally open'
1 = Digital input 'normally closed'
1591
Coolant outlet temperature alarm, lower limit
(2.10.8)
1594
Coolant outlet temperature alarm, upper limit
(2.10.9)
Set here the temperature minimum and maximum limits for the coolant. If the temperature
goes below or exceeds the set limits a warning is instigated.
1595
Coolant outlet temperature fault, upper limit
(2.10.10)