Description of parameters
vacon • 49
24-hour s358 (0)40 837 1150 • Email: [email protected]
1503
Delayed
fault
(2.10.12)
If the sensor signals of too low a coolant flow in the system and the duration of this state
exceeds the time set with this parameter, a fault is activated. Additionally, the
Cooling OK
signal is removed and the frequency converter stops.
1504
Coolant inlet pressure,
minimum
(2.10.2.)
1505
Coolant inlet pressure,
maximum
(2.10.3.)
With these parameters, you can define the value for the minimum and maximum coolant inflow
pressures of the pressure range in bar.
1509
Temperature sensor,
minimum
value
(2.10.6)
1510
Temperature sensor,
maximum value
(2.10.7)
1513
Relay
output 2
function
(2.3.5.2)
See Table 30 at parameter
1514
Constant
speed
(2.10.1)
The constant speed reference can be set with this parameter when the PID control is enabled.
1515
Relay
output
3
function
(2.3.6.2)
Setting value
Signal content
0 = Not used
Out of operation
1 = Cooling OK
2 = Pump 1
3 = Pump 2
Table 33. Output signals via relay outputs RO3 and RO4.
1517
AI3 custom setting minimum
(2.2.18)
1518
AI3 custom setting maximum
(2.2.19)
See parameters
1520
AI3
signal
range
(2.2.16)
0 Signal range 0...20 mA
1 Signal range 4...20 mA
1526
AI3
signal
filter
time
(2.2.21)
See parameter
1529
AI3
signal
inversion
(2.2.20)
See parameter